Fig. 65
1.
Pull out the leads at temperature limiter
A
.
2.
Check the continuity of the temperature limiter with
a multimeter.
3.
Remove faulty temperature limiter.
4.
Coat the new temperature limiter with heat conduct-
ing paste and install it.
5.
After commissioning, press reset button
R
on the
control unit.
Checking the fuse/MCB
F1
A
Fig. 66
1.
Switch off the power supply.
2.
Release the side closures and pivot the control unit
down.
3.
Remove cover
A
.
4.
Check fuse F1 (see connection and wiring dia-
gram).
Troubleshooting
Maintenance
(cont.)
5773 216 GB
Diagnosis