background image

44

A

Fig. 38

1. 

Check the static pressure of the DHW line down-
stream of the pressure reducer and adjust if
required. Set value: max. 3.0 bar (0.3 MPa).

2. 

Close the on-site shut-off valve in the cold water
line.

3. 

Turn operating lever of valve 

A

 to the "front" posi-

tion.

4. 

Check the pre-charge pressure of the DHW expan-
sion vessel and adjust if required. Set value: Static
pressure minus 0.2 bar (0.02 MPa).

5. 

Turn operating lever of valve 

A

 back to the "left"

position and open the on-site shut-off valve in the
cold water line.

Checking the function of the safety valves

Checking the firm seating of electrical connections

Checking all gas equipment for tightness at operating pressure

Danger

Escaping gas leads to a risk of explosion.
Check all gas equipment for tightness.

Note

Only use suitable and approved leak detection agents
(EN 14291) and devices for the tightness test. Leak
detection agents with unsuitable constituents (e.g.
nitrites, sulphides) can cause material damage.
Remove residues of the leak detection agent after test-
ing.

Checking the combustion quality

The electronic combustion controller automatically
ensures optimum combustion quality. During commis-
sioning/maintenance, only the combustion values need
to be checked. For this, measure the CO content and
the CO

2

 or O

2

 content. For a description of the elec-

tronic combustion controller functions, see page 133.

Note

Operate the appliance with uncontaminated combus-
tion air to prevent operating faults and damage.

CO content

The CO content must be < 1000 ppm for all gas
types.

CO

2

 or O

2

 content

The CO

2

 content must be within the following limits

for upper and lower heating output respectively:

7.5 to 9.5 % for natural gas E and LL

8.8 to 11.1 % for LPG P

The O

2

 content must be between 4.0 and 7.6 % for

all gas types.

Commissioning, inspection, maintenance

Checking the pre-charge pressure and the DHW expansion vessel (if instal-

led)

5773 216 GB

Summary of Contents for B2TA

Page 1: ...ctors VIESMANN Vitodens 222 F Type B2TA 3 2 to 35 kW Gas condensing storage combi boiler Gas Council No 41 819 15 41 819 16 41 819 17 Natural gas and LPG versions For applicability see the last page VITODENS 222 F 5773 216 GB 10 2015 Please keep safe ...

Page 2: ...er Hot surfaces can cause burns Before maintenance and service work switch OFF the appliance and let it cool down Never touch hot surfaces on the boiler burner flue system or pipework Please note Electronic assemblies can be damaged by elec trostatic discharge Prior to commencing work touch earthed objects such as heating or water pipes to dis charge static loads Repair work Please note Repairing ...

Page 3: ...ocked flue systems or an inade quate supply of combustion air can cause life threatening poisoning from carbon monoxide in the flue gas Ensure the flue system is in good working order Vents for supplying combustion air must be non closable Extractors Operating appliances that extract air to the outside cooker hoods extractors air conditioning units etc can create negative pressure If the boiler is...

Page 4: ...9 Power supply for accessories at plug lH 230 V 20 Power supply fÖ 21 Routing the connecting cables and leads 21 Closing the control unit enclosure 22 Fitting the front panels 23 4 Commissioning inspec tion maintenance Steps commissioning inspection and maintenance 24 5 Codes Coding level 1 55 Calling up coding level 1 55 General Group 1 55 Boiler Group 2 57 DHW Group 3 57 Heating circuit Group 5 ...

Page 5: ...scription Constant temperature control unit 120 Heating mode 120 DHW heating 120 Weather compensated control unit 120 Heating mode 121 Heating the DHW loading cylinder from cold 121 Reheating when DHW is drawn off 121 Boosting DHW heating 121 Internal extensions 122 Internal extension H1 122 Internal extension H2 123 External extensions accessories 124 AM1 extension 124 EA1 extension 125 Control f...

Page 6: ...6 14 Certificates Declaration of conformity 139 Manufacturer s certificate according to the 1st BImSchV Germany 139 15 Keyword index 140 Index Index cont 5773 216 GB ...

Page 7: ...llec tion point Do not dispose of component in domestic waste The steps in connection with commissioning inspec tion and maintenance are found in the Commission ing inspection and maintenance section and identified as follows Symbol Meaning Steps required during commissioning Not required during commissioning Steps required during inspection Not required during inspection Steps required during mai...

Page 8: ... storage combi boiler with Inox Radial heating surface and the following integrated compo nents Modulating MatriX cylinder burner for natural gas Loading cylinder 100 or 130 l capacity Hydraulics with 3 way diverter valve and variable speed high efficiency circulation pump Vitotronic 100 for constant temperature mode or Vitotronic 200 for weather compensated mode Integral diaphragm expansion vesse...

Page 9: ...ws sample connection sets for installation on finished walls with connection to the top or side 100 569 46 40 50 c d e f g h k l m n p a b 140 50 320 361 398 410 80 Fig 1 q 50 595 50 600 55 220 330 G C A B F D E Fig 2 A Heating flow R B DHW R C Gas connection R D Cold water R E Heating return R F DHW circulation R separate accessory G Condensate drain facing backwards into the wall H Condensate dr...

Page 10: ...r creating pota ble water installations safety valves must be drained directly via a visible unrestricted drain or via a short outlet line to the drain network Note Do not connect the DHW cylinder safety valve to hose L Never change the position of hose L used for ventilation 3 Route condensate hose M to the back drain in wall G or to side aperture H see page 9 Route the condensate hose with a U b...

Page 11: ...charge pipe outlet point D Shut off valve E Flow regulating valve installation recommended F Pressure gauge connection G Non return valve H Drain K Cold water L Drinking water filter M Pressure reducer to DIN 1988 2 Dec 1988 issue N Non return valve pipe separator O Cold water connection at connection set accesso ries Preparing for installation Preparing for boiler installation cont 5773 216 GB In...

Page 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...

Page 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...

Page 14: ... and BS 5440 building regulations GB only Connecting the balanced flue pipe Flue system installation instructions Do not carry out commissioning until the following conditions are met Free passage through the flue gas pipes Flue system with positive pressure is gas tight Apertures for ensuring sufficient combustion air sup ply are open and cannot be closed off Applicable regulations on installing ...

Page 15: ...st Leak detection agents with unsuitable constitu ents e g nitrides sulphides can cause material damage Remove leak detection agent residues after testing Please note Excessive test pressure will damage the boiler and the gas train Max test pressure 150 mbar 15 kPa If a higher pressure is required for tightness tests disconnect the boiler and the gas train from the main supply pipe undo the fittin...

Page 16: ...te Electronic assemblies can be damaged by elec trostatic discharge Prior to commencing any work touch earthed objects such as heating or water pipes to dis charge static loads Installing the boiler Opening the control unit enclosure 5773 216 GB Installation ...

Page 17: ...sembly eas ier Outside temperature sensor Flow temperature sensor for low loss header accessories A Radio clock receiver X4 KM BUS connection variable speed heating cir cuit pump if installed aVG KM BUS subscriber accessories To connect several accessories see page 20 Vitotrol 200A or 300A remote control Vitocom 100 type GSM Mixer extension kit AM1 extension EA1 extension Wireless base station KM ...

Page 18: ...imum limit coding address 06 in group Boiler 2 Please note Live contacts lead to short circuits or phase fail ure The external connection must be floating and meet the requirements of protection class II Plug lH EA1 extension A lH N 1 L A Floating contact when connected remove jumper between L and 1 B S DE D DE A DE A A Floating contact B EA1 extension Codes 4b 1 in group General 1 Effect of the f...

Page 19: ...ction must be floating and meet the requirements of protection class II Plug lH EA1 extension A lH N 1 L A Floating contact when connected remove jumper between L and 1 B S DE D DE A DE A A Floating contact B EA1 extension Codes 4b 2 in group General 1 Effect of the function on the heating circuit pump Coding address d6 in group Heating circuit only for weather compensated control units Effect of ...

Page 20: ...A aVG aVG f A fÖ aVG aVG f A Fig 12 Some accessories with direct power supply B C A D E fÖ fÖ aVG fÖ lH aVG aVG f A aVG aVG f A fÖ aVG aVG f A Fig 13 A Heat source control unit B Extension kit for heating circuit with mixer M2 C Extension kit for heating circuit with mixer M3 D AM1 extension or EA1 extension E ON OFF switch fÖ Mains input fÖA Power outlet lH Power outlet at the control unit aVG KM...

Page 21: ... requirements In addition we recommend installing an AC DC sen sitive RCD RCD class B for DC fault cur rents that can occur with energy efficient equipment Max fuse rating 16 A Danger The absence of component earthing can lead to serious injury from electric current if an electrical fault occurs The appliance and pipework must be connected to the equipotential bonding of the building Routing the c...

Page 22: ...arately into the control unit support Note The programming unit can also be inserted into a wall mounting base accessories near the boiler Wall mounting base installation instructions Installing the boiler Closing the control unit enclosure 5773 216 GB Installation ...

Page 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...

Page 24: ...alanced flue system annular gap check 34 20 Removing the burner 35 21 Checking the burner gasket and burner gauze assembly 36 22 Checking and adjusting the ignition and ionisation electrodes 37 23 Cleaning the heating surfaces 37 24 Checking the condensate drain and cleaning the siphon 37 25 Installing the burner 39 26 Checking the neutralising system if installed 27 Checking the anode connection ...

Page 25: ...e control unit to the heating system 46 42 Adjusting heating curves 51 43 Connecting the control unit to the LON 52 44 Scanning and resetting the Service display 53 45 Fitting the cover panel and front panels 54 46 Instructing the system user 54 Commissioning inspection maintenance Steps commissioning inspection and cont 5773 216 GB ...

Page 26: ...ftening system for heating water Total permissible hardness of the fill and top up water Total heating output Specific system volume kW 20 l kW 20 l kW to 50 l kW 50 l kW 50 3 0 mol m3 16 8 dH 2 0 mol m3 11 2 dH 0 02 mol m3 0 11 dH 50 to 200 2 0 mol m3 11 2 dH 1 5 mol m3 8 4 dH 0 02 mol m3 0 11 dH 200 to 600 1 5 mol m3 8 4 dH 0 02 mol m3 0 11 dH 0 02 mol m3 0 11 dH 600 0 02 mol m3 0 11 dH 0 02 mol...

Page 27: ... unit Service menu 1 Press OK and å simultaneously for approx 4 s 2 Service functions 3 Filling Filling function is enabled 4 Ending filling function Press OK or ä Service menu 1 Press OK and å simultaneously for approx 4 s 2 Select 4 and confirm with OK ON flashes 3 Activate the filling function with OK bF on is shown constantly 4 Ending filling function Press ä Filling the DHW cylinder on the DH...

Page 28: ...ntrol unit As soon as the time and date have been set the con trol unit automatically checks the function of the flue gas temperature sensor The display shows Flue gas temp sensor test and Active Note If the flue gas temperature sensor is incorrectly posi tioned commissioning is aborted and fault message A3 is shown see page 95 Immediately after being switched on the control unit au tomatically ch...

Page 29: ...red operating pressure has built up close fill valve C Open the shut off valves on the heating water side 7 Remove the drain hose from air vent valve B and retain Venting the heating system A Fig 21 1 Close the gas shut off valve and switch the control unit ON 2 Check whether the air vent screw in quick action air vent valve A of the heating circuit pump is open 3 Activate venting program see foll...

Page 30: ...lashes 3 Activate the venting function with OK EL on is shown constantly 4 Ending venting function Press ä Filling the siphon with water C B A Fig 22 1 Pivot the control unit forwards 2 Remove retaining clip A 3 Pull filler pipe B upwards 4 Remove trap C downwards 5 Fill siphon with water and refit 6 Check that the condensate pipe is connected cor rectly to the siphon and heat exchanger Note Route...

Page 31: ...Gas type conversion on page 31 1 Determine the gas type and Wobbe index by asking your local gas supply utility or LPG supplier 2 For operation with LPG convert the burner see page 31 3 Record the gas type in the report on page 136 Gas type conversion only for operation with LPG 1 2 A Fig 23 1 Set adjusting screw A on the gas train to 2 2 Turn on ON OFF switch 3 Select the gas type in coding addre...

Page 32: ...suitable measuring instrument with a resolu tion of at least 0 1 mbar 0 01 kPa to check the supply pressure 7 Record the actual value in the report on page 136 Implement measures as indicated in the table below 8 Shut down the boiler close the gas shut off valve Remove the pressure gauge and seal test connec tor A with screw 9 Open the gas shut off valve and start the appliance Danger Gas escaping...

Page 33: ...of ionisation electrode Purge the gas line Yes Burner in operation No Shuts down below the set boiler water temperature and restarts immediately Check the flue system for tightness flue gas recircula tion check the gas flow pressure Yes Automatic calibration of the combustion controller No Fault E3 Ensure adequate heat trans fer Press reset button R Fault Eb Check gap between ionisa tion electrode...

Page 34: ...e and confirm with OK Tightness test on balanced flue system annular gap check A Fig 25 A Combustion air aperture ventilation air For balanced flue systems tested together with the heat source there is no requirement for a tightness test overpressure test during commissioning by the flue gas inspector In this case we recommend that your heating contrac tor carries out a simple tightness test durin...

Page 35: ...opening 3 Remove cables from fan motor A gas train B ignition and ionisation electrode C ignition unit D and earth tab E 4 Undo gas supply pipe fitting F 5 Undo four screws G and remove the burner Please note Prevent damage to the burner Never rest the burner on the burner gauze assembly Commissioning inspection maintenance Removing the burner 5773 216 GB ...

Page 36: ...mal insulation ring D and then remove thermal insulation ring D 3 Undo 2 Torx screws and remove burner gauze assembly E with gasket F 4 Insert new burner gauze assembly E with new gasket F and secure Torque 5 0 Nm 5 Fit thermal insulation ring D 6 Fit electrodes B Torque 4 5 Nm Commissioning inspection maintenance Checking the burner gasket and burner gauze assembly 5773 216 GB ...

Page 37: ...Brushing can cause deposits to become lodged in the gaps between the coils Never use brushes to clean the heat exchanger Note Discolouration on the heat exchanger surface is a nor mal sign of use It has no bearing on the function and service life of the heat exchanger The use of chemical cleaning agents is not required A Fig 29 1 Use a vacuum cleaner to remove combustion resi dues from heating sur...

Page 38: ... condensate hose from trap C 6 Clean the siphon 7 Fill siphon with water and reassemble with retaining clip A 8 Check that the condensate pipe is connected cor rectly to the siphon and heat exchanger Note Route the drain hose without any bends and with a constant fall Commissioning inspection maintenance Checking the condensate drain and cleaning the cont 5773 216 GB ...

Page 39: ...scaping gas leads to a risk of explosion Check the fitting for gas tightness 4 Connect the electrical cables leads Fan motor A Ionisation electrode C Gas train B Ignition unit D Earth E Checking the neutralising system if installed Checking the anode connection Check that the earth cable is connected to the magne sium anode Commissioning inspection maintenance Installing the burner 5773 216 GB ...

Page 40: ...end checking the magnesium anode func tion annually This function test can be carried out with out interrupting operation by measuring the earth cur rent with an anode tester Fig 33 1 Remove cover A 2 Remove earth cable B from tab C Commissioning inspection maintenance Checking the anode connection cont 5773 216 GB ...

Page 41: ...tion A operational to lever position B or C as required Lever position B Drain drinking water circuit in appliance excluding DHW cylinder via the cold water connection Lever position C Drain drinking water circuit in appliance and DHW cylinder via the DHW con nection The cold water connection remains filled Cleaning the loading cylinder Note According to EN 806 a visual inspection and if neces sar...

Page 42: ... loading cylinder after cleaning Checking and replacing the magnesium anode if required Check the magnesium anode If it is discovered that the anode has degraded to 10 to 15 mm Ø we recom mend replacing the magnesium anode Re assembling and filling the loading cylinder Fig 36 1 Reconnect the loading cylinder to the pipework 2 Insert new gasket A underneath flange cover B 3 Fit flange cover B and t...

Page 43: ...tem 1 Drain the system until the pressure gauge shows 0 2 If the expansion vessel pre charge pressure is lower than the static system pressure Top up with nitrogen at connection A until the pre charge pres sure is 0 1 to 0 2 bar 10 to 20 kPa higher than the static system pressure 3 Top up with water until the charge pressure of the cooled system is 0 1 to 0 2 bar 10 to 20 kPa higher than the pre c...

Page 44: ... the tightness test Leak detection agents with unsuitable constituents e g nitrites sulphides can cause material damage Remove residues of the leak detection agent after test ing Checking the combustion quality The electronic combustion controller automatically ensures optimum combustion quality During commis sioning maintenance only the combustion values need to be checked For this measure the CO...

Page 45: ...easures detailed on page 44 8 After testing press OK 9 Enter the actual value into the report Select higher lower heating output Weather compensated control unit Constant temperature control unit Service menu 1 Press OK and å simultaneously for approx 4 s 2 Actuator test 3 Select the lower heating output Select Base load OFF Then Base load ON ap pears and the burner operates at its lower heating o...

Page 46: ...ndividual coding steps see page 55 System version 1 One heating circuit without mixer A1 4 3 1 2 Fig 40 1 Vitodens 222 F 2 Outside temperature sensor only for weather compensated control units 3 Vitotrol 100 only for constant temperature control units 4 Heating circuit without mixer A1 heating circuit 1 Function system components Code Settings Group Operation with LPG 82 1 General 1 System with DH...

Page 47: ...sor M2 6 Heating circuit pump M2 7 Extension kit mixer M2 8 Low loss header 9 Flow temperature sensor low loss header Function system components Code Settings Group Operation with LPG 82 1 General System with only one heating circuit with mixer and DHW heating 00 4 General System with DHW circulation pump DHW circulation pump connected at internal H1 or H2 extension System with low loss header 04 ...

Page 48: ... circuit pump M2 8 Extension kit mixer M2 Note The flow rate of the heating circuit without mixer must be at least 30 greater than the flow rate of the heat ing circuit with mixer Function system components Code Settings Group Operation with LPG 82 1 General System with only one heating circuit with mixer with extension kit for mixer without unregulated heating circuit with DHW heating 00 4 Genera...

Page 49: ...ms 6 Flow temperature sensor M2 7 Heating circuit pump M2 8 Extension kit mixer M2 9 Heat exchanger for system separation qP Assembly kit with mixer accessories Function system components Code Settings Group Operation with LPG 82 1 General System with only one heating circuit with mixer with extension kit for mixer without unregulated heating circuit with DHW heating 00 4 General System with DHW c...

Page 50: ...perature sensor M3 qW Heating circuit pump M3 qE Extension kit mixer M3 qR Low loss header qT Flow temperature sensor low loss header Function system components Code Settings Group Operation with LPG 82 1 General System with only 2 heating circuits with mixer with extension kit for mixer without unregulated heating circuit with DHW heating 00 8 General System without DHW circulation pump Heating c...

Page 51: ...n C Slope 2 4 2 6 2 8 3 0 3 2 3 4 90 80 70 60 50 40 30 0 5 10 15 20 5 10 2 0 2 2 Set room temperature in C 35 30 25 20 15 10 5 0 4 0 6 0 8 1 0 1 2 1 4 30 25 1 8 1 6 Fig 45 Slope setting ranges Underfloor heating systems 0 2 to 0 8 Low temperature heating systems 0 8 to 1 6 Selecting the set room temperature Individually adjustable for each heating circuit The heating curve is offset along the axis...

Page 52: ...rding to the system requirements Connecting the control unit to the LON The LON communication module must be plugged in Note The data transfer via LON can take several minutes Example Single boiler system with Vitotronic 200 H and Vitocom 200 Set the LON subscriber numbers and further functions via code 2 see the following table Note The same subscriber number must not be allocated twice within th...

Page 53: ...Service functions 3 Subscriber check 4 Select subscriber e g subscriber 10 5 Start the subscriber check with OK Successfully tested subscribers are designated with OK Unsuccessfully tested subscribers are identified with Not OK Note To perform another subscriber check Create a new subscriber list with Delete list sub scriber list is updated Note During the subscriber check the display of the relev...

Page 54: ...un and in terval restart at 0 Fitting the cover panel and front panels Fit the cover panel see position A in diagram on page 29 Fit the front panels see page 23 Instructing the system user The system installer should hand the operating instruc tions to the system user and instruct the user in oper ating the system This includes all components installed as accessories e g remote control units In ad...

Page 55: ...device In this group all coding addresses from coding level 1 are displayed in ascending order 7 Standard setting Call up code 1 Service menu 1 Press OK and å simultaneously for approx 4 s 2 Coding level 1 3 Select group of required coding address 4 Select coding address 5 Set the value according to the following tables and confirm with OK Service menu 1 Press OK and å simultaneously for approx 4 ...

Page 56: ...Coding in the delivered condition Possible change Internal circulation pump function 51 0 The internal circulation pump al ways starts when there is a heat demand 51 1 System with low loss header The internal circulation pump only starts upon heat demand if the burn er is running Circulation pump stops on expiry of the run on time 51 2 System with heating water buffer cylinder The internal circula...

Page 57: ...g Coding in the delivered condition Possible change Single multi boiler system 01 1 Do not adjust only for constant temperature control units Burner service in 100 hours 21 0 No service interval set in hours run 21 1 to 21 100 The number of hours run before the burner should be serviced is adjust able from 100 to 10 000 h One adjusting step 100 h Service interval in months 23 0 No time set for bur...

Page 58: ...ts A5 0 Without heating circuit pump logic function A5 1 to A5 15 With heating circuit pump logic func tion Heating circuit pump OFF see following table Parameter address A5 With heating circuit pump logic function Heating circuit pump OFF 1 OT RTset 5 K 2 OT RTset 4 K 3 OT RTset 3 K 4 OT RTset 2 K 5 OT RTset 1 K 6 OT RTset 7 to OT RTset 1 K 15 OT RTset 9 K Coding in the delivered condition Possib...

Page 59: ...g circuit with mixer and remote control Heating mode reduced mode Weather compensated only for weather compensated control units b0 1 Heating mode Weather compensa ted Reduced mode With room tempera ture hook up b0 2 Heating mode With room tempera ture hook up Reduced mode Weather compen sated b0 3 Heating mode reduced mode With room temperature hook up Economy function room temperature b5 0 Only ...

Page 60: ...rature Ext heating program changeover to heating circuit d8 0 With EA1 extension No operating program changeover d8 1 Operating program changeover via input DE1 d8 2 Operating program changeover via input DE2 d8 3 Operating program changeover via input DE3 Max pump speed in standard mode E6 Only for heating systems without a heating circuit with mixer Maximum speed of the internal speed controlled...

Page 61: ...o F7 24 In Standby mode the internal cir culation pump will be started 1 to 24 times per day for 10 min each time Start temperature raising F8 5 Temperature limit for terminating reduced mode 5 C see example on page 130 Observe the setting of coding ad dress A3 Only for weather com pensated control units F8 10 to F8 60 Temperature limit adjustable from 10 to 60 C F8 61 Function not active End temp...

Page 62: ...sses are displayed in ascending order Standard setting 1 General 2 Boiler 3 DHW 4 Solar 5 Heating circuit 1 6 All codes std device In this group all coding addresses from coding level 2 are displayed in ascending order 7 Standard setting Call up code 2 Service menu 1 Press OK and simultaneously for approx 4 s 2 Press OK and simultaneously for approx 4 s 3 Coding level 2 4 Select group of required ...

Page 63: ...ding addresses for the combustion control parame ters 11 9 Access to the coding addresses for the combustion control parameters is open 25 0 Without outside temperature sen sor for constant temperature con trol units 25 1 With outside temperature sensor automatic recognition 2A 0 Without wireless outside tempera ture sensor 2A 1 With wireless outside temperature sensor automatic recognition 2A 2 W...

Page 64: ... 3F in this group 3b 3 Function of DE2 input External blocking Internal circulation pump function Coding address 3E in this group 3b 4 Function of DE2 input External blocking with fault message input Internal circulation pump function Coding address 3E 3b 5 Function of DE2 input Fault mes sage input 3b 6 Function of DE2 input Brief opera tion of DHW circulation pump push button function Adjustment...

Page 65: ...expiry of the run on time 51 2 System with heating water buffer cylinder The internal circulation pump only starts upon heat demand if the burn er is running Circulation pump stops on expiry of the run on time 52 0 Without flow temperature sensor for low loss header 52 1 With flow temperature sensor for low loss header automatic recognition 53 1 Function of terminal sÖ sK of inter nal H1 H2 extens...

Page 66: ...n C Cel sius 88 1 Temperature displayed in F Fah renheit 8A 175 Do not adjust 8F 0 Control in standard menu and in extended menu is enabled Note The respective code is only activa ted when you exit the service menu see page 75 8F 1 Control in standard menu and in ex tended menu is locked Emissions test mode can be ena bled 8F 2 Control in standard menu is ena bled but locked in extended menu Emiss...

Page 67: ...t Boiler for weather compensated control units see page 62 Select 2 for constant temperature control unit see page 62 Coding Coding in the delivered condition Possible change 04 1 Minimum burner pause time sub ject to the boiler load specified by boiler coding card 04 0 Systems with low loss header Pause time set permanently speci fied by boiler coding card 06 Maximum limit of the boiler water tem...

Page 68: ...see page 62 Coding Coding in the delivered condition Possible change 56 0 Set DHW temperature adjustable from 10 to 60 C 56 1 Set DHW temperature adjustable from 10 to above 60 C Note Max value subject to boiler coding card Observe the maximum permissible DHW temperature 57 0 Do not adjust 58 0 Without auxiliary function for DHW heating 58 10 to 58 60 Input of a 2nd set DHW tempera ture adjustable...

Page 69: ...to set val ue 2 73 0 DHW circulation pump ON ac cording to time program only for weather compensated control units 73 1 to 73 6 During time program ON from once per hour for 5 min to ON 6 times per hour for 5 min 73 7 Constantly ON Heating circuit Group 5 Select Heating circuit for weather compensated control unit see page 62 Select 5 for constant temperature control unit see page 62 Coding Coding...

Page 70: ...address A3 A5 5 With heating circuit pump logic function economy control Heat ing circuit pump is OFF when the outside temperature OT is 1 K higher than the set room tempera ture RTset OT RTset 1 K only for weather compensated control units A5 0 Without heating circuit pump logic function A5 1 to A5 15 With heating circuit pump logic func tion Heating circuit pump OFF see following table Parameter...

Page 71: ...time Heating cir cuit pump OFF if the set value is altered through a change in oper ating mode or through a change in the set room temperature only for weather compensated control units A9 0 Without pump idle time A9 1 to A9 15 With pump idle time adjustable from 1 to 15 1 short idle time 15 long idle time b0 0 Only for heating circuit with mixer and remote control Heating mode reduced mode Weathe...

Page 72: ... 0 d4 13 to d4 40 Heating curve level adjustable from 13 to 40 see page 51 d5 0 With external heating program changeover observe setting for coding addresses 3A 3b and 3C in the General group Operating program switches to Constant central heating with re duced room temperature or Standby mode subject to the settings of the set reduced room temperature only for weather compensated control units d5 ...

Page 73: ...ixer Minimum speed of the internal speed controlled heating circuit pump for operation with reduced room temperature subject to the setting in coding address E9 on ly for weather compensated con trol units E8 0 Speed corresponding to setting in coding address E7 E9 45 Only for heating systems without a heating circuit with mixer Speed of the internal speed con trolled heating circuit pump 45 of th...

Page 74: ...he internal cir culation pump will be started 1 to 24 times per day for 10 min each time F8 5 Temperature limit for terminating reduced mode 5 C see example on page 130 Observe the setting of coding ad dress A3 Only for weather com pensated control units F8 10 to F8 60 Temperature limit adjustable from 10 to 60 C F8 61 Function not active F9 14 Temperature limit for raising the re duced set room t...

Page 75: ...t 2 HC2 DHW Enter Vitocom PIN code Subscriber check Service PIN LON Heating circuit 3 HC3 Coding level 2 Fault history Service functions Terminate service Reset data Filling Venting Max output Service reset Multi boiler system Fig 49 Note Do not adjust menu point Multi boiler system This menu point changes the control unit to a constant temperature control unit in a multi boiler system Diagnosis O...

Page 76: ...u 1 Press OK and å simultaneously for approx 4 s 2 Select required information with 3 Confirm with OK flashes 4 Confirm with OK the value is reset Brief scan In the brief scan you can scan temperatures software versions and connected components for example Weather compensated control unit Service menu 1 Press OK and å simultaneously for approx 4 s 2 Diagnosis 3 Brief scan 4 Press OK The display sh...

Page 77: ...or Vitocomfort Software ver sion remote control Remote con trol 0 Without 1 Vitotrol 200A 200 RF 2 Vitotrol 300A 300 RF or Vitocomfort Software ver sion remote control 10 Only for KM BUS circula tion pumps Internal circulation pump 0 0 0 0 Speed con trolled pump 0 Without 1 Wilo 2 Grundfos Software ver sion speed controlled pump 0 No variable speed pump 11 0 0 Software ver sion Mixer exten sion he...

Page 78: ...ontrol unit d Speed controlled pump 1 Wilo 2 Grundfos Software version Speed controlled pump 0 No speed con trolled pump E 1 Software version Burner control unit F 1 Setting of cod ing address 53 Internal details for calibration AM1 extension F 2 Software ver sion Output A1 config uration value corre sponds to coding address 33 set ting Output A1 switching state 0 OFF 1 ON Output A2 con figuration...

Page 79: ...g circuit pump output active extension to heating circuit with mixer Mixer HC2 Open Mixer open output active extension to heating circuit with mixer Mixer HC2 Close Mixer close output active extension to heating circuit with mixer Heating circuit pump HC3 ON Heating circuit pump output active extension to heating circuit with mixer Mixer HC3 Open Mixer open output active extension to heating circu...

Page 80: ...e internal circulation pump 4 Diverter valve set to heating mode 5 Diverter valve in central position filling draining 6 Diverter valve set to DHW heating 10 Output sÖ sK at internal H1 H2 extension enabled 19 Contact P S at plug aBJ of EA1 extension closed 20 Output A1 at AM1 extension active 21 Output A2 at AM1 extension active 22 Internal output sA active circulation pump for cylinder heating D...

Page 81: ...rom the fault memory fault history The 10 most recent faults including resolved ones are saved and can be scanned Faults are sorted by date 1 Press OK and å simultaneously for approx 4 s 2 Fault history 3 Display Deleting fault history 1 Press OK and å simultaneously for approx 4 s 2 Fault history 3 Delete Constant temperature control unit In the event of a fault red fault indicator A flashes The ...

Page 82: ...emperature were 0 C Lead break out side temperature sensor Check outside tempera ture sensor see page 91 19 X X Regulates as if the outside temperature were 0 C Communication er ror wireless out side temperature sensor Check wireless connec tion place wireless out side temperature sensor close to the wireless base station Log off outside temperature sensor then log on again Replace if required see...

Page 83: ...mpera ture sensor see page 92 59 X X No DHW heating Lead break outlet temperature sen sor Check the outlet tempera ture sensor see page 93 A7 X Control mode as per delivered condition Programming unit faulty Replace programming unit A8 X Burner blocked The venting program is started automatically see page 55 Air in the internal circulation pump or minimum flow rate not achieved Vent the system if ...

Page 84: ... cir cuit 5 and remote con trol configuration see page 132 For wireless remote con trols Check connection place remote control unit close to the boiler bd X Control mode without remote control Communication er ror Vitotrol remote control heating cir cuit 2 with mixer Check connections ca ble coding address A0 in group Heating cir cuit 5 and remote con trol configuration see page 132 For wireless r...

Page 85: ...ned d7 X X Control mode DE2 input at EA1 extension reports a fault Remove fault at appliance concerned d8 X X Control mode DE3 input at EA1 extension reports a fault Remove fault at appliance concerned dA X Control mode without room influence Short circuit room temperature sen sor heating circuit 1 without mixer Check room temperature sensor heating circuit 1 db X Control mode without room influen...

Page 86: ...t down Ensure adequate heat transfer Press reset button R E4 X X Burner blocked 24 V power supply fault Replace control unit E5 X X Burner blocked Flame amplifier fault Replace control unit E6 X X Burner blocked System pressure too low Top up with water E7 X X Burner in a fault state Ionisation current too low during cali bration Check ionisation elec trode Distance to burner gauze assembly see pa...

Page 87: ...urn er gauze assembly see page 37 Check assignment of gas type see page 37 Check flue system reme dy flue gas recirculation if required Press reset button R EC X X Burner in a fault state Parameter fault during calibration Press reset button R or Replace boiler coding card and press reset but ton R Ed X X Burner in a fault state Internal fault Replace control unit EE X X Burner in a fault state Fl...

Page 88: ...re limiter and connecting cables Press reset button R F3 X X Burner in a fault state Flame signal is al ready present at burner start Check ionisation elec trode and connecting ca ble Press reset button R F8 X X Burner in a fault state Fuel valve closes too late Check gas train Check both control paths Press reset button R F9 X X Burner in a fault state Fan speed too low during burner start Check ...

Page 89: ...cessa ry FF X X Burner blocked or in a fault state Internal fault or re set button R disa bled Restart the appliance Re place the control unit if the appliance will not re start Note If subscriber faults occur Subscriber fault is dis played Maintenance Please note Residual water will escape when the boiler or one of the following components is fitted or removed Water filled pipework Circulation pu...

Page 90: ...sition 1 2 3 Fig 54 Drain boiler on the heating water side Fig 55 1 Close the shut off valves on the heating water side 2 Route hose at drain valve A into a suitable con tainer or drain outlet 3 Open drain valve A and drain the boiler the graphic not in this document setas much as required Troubleshooting Maintenance cont 5773 216 GB Diagnosis ...

Page 91: ...the resistance of the outside temperature sen sor across terminals X3 1 and X3 2 on the dis connected plug and compare it with the curve 3 Where actual values deviate severely from the curve values disconnect the wires at the sensor and repeat the test on the sensor itself 4 Depending on the result replace the lead or the outside temperature sensor Troubleshooting Maintenance cont 5773 216 GB Diag...

Page 92: ...or Pull out the leads at boiler water temperature sen sor A and check the resistance Cylinder temperature sensor Pull plug from the cable harness at the control unit and check the resistance Flow temperature sensor Pull out plug X3 at the control unit and check the resistance across terminals X3 4 and X3 5 Troubleshooting Maintenance cont 5773 216 GB Diagnosis ...

Page 93: ...ing water side before replacing the sensor Checking the outlet temperature sensor Fig 60 10 1 10 30 50 70 90 110 Temperature in C 0 4 0 6 0 8 2 4 6 8 20 Resistance in kΩ Fig 61 Sensor type NTC 10 kΩ 1 Pull leads from outlet temperature sensor A 2 Check the sensor resistance and compare it to the curve 3 In the event of severe deviation replace the sensor Danger The outlet temperature sensor is dir...

Page 94: ...e heat exchanger C to the front 6 Check the connections on the heating water and DHW side for contamination and scaling if required replace the plate heat exchanger 7 Install in reverse order using new gaskets Checking the flue gas temperature sensor The flue gas temperature sensor locks the boiler if the permissible flue gas temperature is exceeded After the flue system has cooled down press the ...

Page 95: ...re sensor is not positioned correctly commissioning is cancelled and fault mes sage A3 is displayed 1 Check whether the flue gas temperature sensor is correctly inserted See previous diagram 2 If necessary correct the position of the flue gas temperature sensor or replace faulty flue gas tem perature sensor 3 Press reset button R and repeat commissioning The check is repeated until it is completed...

Page 96: ...w temperature limiter with heat conduct ing paste and install it 5 After commissioning press reset button R on the control unit Checking the fuse MCB F1 A Fig 66 1 Switch off the power supply 2 Release the side closures and pivot the control unit down 3 Remove cover A 4 Check fuse F1 see connection and wiring dia gram Troubleshooting Maintenance cont 5773 216 GB Diagnosis ...

Page 97: ...o Open The flow temperature sensor must now capture a higher temperature If the temperature drops either the motor is turning in the wrong direction or the mixer insert is incorrectly fitted Mixer installation instructions Changing the rotational direction of the mixer motor if required gS BU Fig 67 1 Remove the upper casing cover of the extension kit Danger An electric shock can be life threateni...

Page 98: ... H accessories The Vitotronic 200 H is connected to the control unit via the LON cable To test the connection carry out a subscriber check at the boiler control unit see page 53 Troubleshooting Maintenance cont 5773 216 GB Diagnosis ...

Page 99: ...llowing information is required Serial no see type plate A Assembly from the parts list Position number of the individual part within the assembly from this parts list Parts lists Overview of assemblies 5773 216 GB Components ...

Page 100: ...sing assembly C Hydraulic assembly with hydraulic block D Loading cylinder assembly E Heat cell assembly with MatriX cylinder burner F Control unit assembly G Miscellaneous assembly Parts lists Overview of assemblies cont 5773 216 GB Components ...

Page 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...

Page 102: ...102 0003 0006 0005 0005 0013 0014 0014 0004 0010 0014 0002 0014 0001 0005 0014 0002 0014 0007 0009 0008 0012 0011 Fig 70 Parts lists Casing 5773 216 GB Components ...

Page 103: ...ed seal 0005 Profiled seal 0006 Adjustable foot 0007 Control unit support 0008 Side panel right 0009 Side panel left 0010 Loading cylinder mounting bracket 0011 Top panel insert 0012 Top panel 0013 Front panel bottom 0014 Fixings for location stud 2 pce Parts lists Casing cont 5773 216 GB Components ...

Page 104: ...7 0042 0049 0049 0048 0041 0007 0042 0046 0042 0007 0015 0042 0046 0002 0041 0047 0004 0007 0027 0041 0013 0028 0045 0041 0042 0021 0046 0007 0015 0023 0024 0031 0002 0047 0044 0016 0044 0041 0025 0012 0012 0012 0011 0004 0014 0014 0010 0015 0038 0040 0041 0012 0009 0044 0016 0044 0012 0012 0017 0041 0035 0006 0047 0008 0009 0043 0005 0033 0029 0003 0047 0002 0036 0008 0012 0030 0020 0005 0046 Fig...

Page 105: ... Expansion vessel connection line G 3 8 0021 Cold water hydraulic connection 0022 Pump motor 0023 CIL casing 0024 Cartridge non return valve 0025 Shut off valve cold water cylinder 0026 Circular seal washer 8 x 2 5 pce 0027 Connection line DHW charging 0028 Shut off valve DHW cylinder 0029 Flow pipe 0030 Expansion vessel 0031 Connection pipe cold water 0032 Connection pipework heating water return...

Page 106: ... pce 0045 Cap G 3 4 SW 30 0046 Gasket A 10 x 15 x 1 5 5 pce 0047 O ring 17 86 x 2 62 5 pce 0048 O ring 14 3 x 2 4 0049 Spring clip DN 25 5 pce 0050 Plug 0051 Gasket A 23 x 30 x 2 orange 5 pce Parts lists Hydraulics cont 5773 216 GB Components ...

Page 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...

Page 108: ...5 0002 0015 0016 0014 0015 0016 0012 0014 0016 0016 0014 0004 0017 0006 0010 0015 0013 0001 0016 0005 0005 0003 0016 0003 0005 0011 0012 0002 0016 0003 0016 0018 0007 Fig 72 Parts lists Hydraulic block 5773 216 GB Components ...

Page 109: ...acket 0008 Plate heat exchanger insulation board 0009 Plate heat exchanger insulation shell 0010 Overflow line 0011 Flow unit 0012 Valve insert 0013 Overflow valve 0014 O ring 17 86 x 2 62 5 pce 0015 Gasket A 17 x 24 x 2 5 pce 0016 O ring 9 6 x 2 4 5 pce 0017 Temperature sensor 0018 Plate heat exchanger Parts lists Hydraulic block cont 5773 216 GB Components ...

Page 110: ...110 0002 0010 0004 0001 0003 0004 0005 0009 0006 0007 0008 0007 Fig 73 Parts lists Loading cylinder 5773 216 GB Components ...

Page 111: ...rain relief 0003 Magnesium anode 0004 Gasket 0005 Flange with gasket 0006 Cover 0007 Gasket 23 x 30 x 2 5 pce 0008 Sleeve 0009 Flange insulation 0010 Cylinder temperature sensor NTC 10kΩ Parts lists Loading cylinder cont 5773 216 GB Components ...

Page 112: ...0022 0015 0017 0025 0005 0024 0025 0002 0014 0017 0015 0008 0022 0010 0020 0020 0009 0021 0005 0024 0001 0007 0006 0019 0002 0018 0013 0017 0017 0017 0004 0008 0017 0016 0017 0003 0017 0023 0025 Fig 74 Parts lists Heat cell 5773 216 GB Components ...

Page 113: ...0011 Heat exchanger 0012 Gas pipe 0013 Condensate hose 0014 O rings 35 4 x 3 59 5 pce 0015 Gasket A 17 x 24 x 2 5 pce 0016 Hose 19 x 600 corrugated 0017 Spring clip DN 25 5 pce 0018 Hose 19 x 270 corrugated 0019 Hose 19 x 500 corrugated 0020 Plug for boiler flue connection 0021 Gasket DN 60 0022 Diaphragm grommet 5 pce 0023 Connection elbow heating water return 0024 Thermal insulation block 0025 O...

Page 114: ... 0014 0004 0018 0003 0018 0006 0004 0018 0019 0019 0001 0004 0007 0012 0013 0013 0012 0007 0013 0012 0005 0011 0017 0007 0009 0016 0008 0015 0002 0001 Fig 75 Parts lists MatriX cylinder burner 5773 216 GB Components ...

Page 115: ... door flange wearing part 0008 Radial fan 0009 Gas train 0010 Burner door 0011 Ignition unit 0012 Gasket ionisation electrode 5 pce 0013 Gasket ignition electrode 5 pce 0014 Blade terminal 10 pce 0015 Mixture restrictor 0016 Gas nozzle 13 kW 19 kW 02 yellow 26 kW 04 grey 35 kW 06 black 0017 Venturi extension 0018 Mounting plate thermal insulation ring 2 pce 0019 Gasket DN 65 Parts lists MatriX cyl...

Page 116: ...116 0002 0008 0009 0003 0020 0021 0014 0017 0018 0001 0015 0006 0007 0010 0011 0012 0019 0015 0004 0005 0013 0015 0009 0005 Fig 76 Parts lists Control unit 5773 216 GB Components ...

Page 117: ... LON communication module 0009 PCB adaptor 0010 Cable harness X8 X9 ionisation 0011 Cable harness 100 35 54 PE 0012 Power cable stepper motor 0013 Mating plug set 0014 Cable fixing 0015 Locking bolts left and right 0017 Wireless outside temperature sensor 0018 Outside temperature sensor hardwired 0019 KM BUS connecting cable 145 0020 Internal H1 extension 0021 Internal H2 extension Parts lists Con...

Page 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...

Page 119: ...paint white 0003 Touch up paint stick white 0004 Installation and service instructions 0005 Operating instructions for constant temperature mode 0006 Operating instructions for weather compensated mode Parts lists Miscellaneous cont 5773 216 GB Components ...

Page 120: ...g range 20 to 74 C DHW heating The burner the circulation pump and the 3 way valve are started or changed over if the cylinder temperature lies 2 5 K below the set cylinder temperature In the delivered condition the set boiler water temper ature is 20 K above the set cylinder temperature adjustable via coding address 60 in group DHW The burner will be switched off and the circulation pump run on t...

Page 121: ...has been reached at the cylinder temperature sensor After loading has stopped the cylinder loading pump and the 3 way diverter valve remain on for a further 30 s Reheating when DHW is drawn off When DHW is drawn off cold water enters the lower section of the loading cylinder The heating circuit pump is switched ON and the 3 way diverter valve is changed over if the cylinder tem perature sensor cap...

Page 122: ... General Central fault message code 53 0 DHW circulation pump code 53 1 only for weather compensated operation Connect DHW circulation pumps with standalone functions directly to the 230 V supply Heating circuit pump for heating circuit without mixer code 53 2 Circulation pump for cylinder heating code 53 3 An external safety valve can be connected to connec tion gD Function description Internal e...

Page 123: ...tral fault message code 53 0 DHW circulation pump code 53 1 only for weather compensated operation Connect DHW circulation pumps with standalone functions directly to the 230 V supply Heating circuit pump for heating circuit without mixer code 53 2 Circulation pump for cylinder heating code 53 3 An extractor fan can be switched off via connection aBJ when the burner starts Function description Int...

Page 124: ...ec ted to each of the connections A1 and A2 Heating circuit pump for the heating circuit without mixer Circulation pump for cylinder heating DHW circulation pump Connect DHW circulation pumps with standalone functions directly to the 230 V supply Select the output functions by means of the codes on the boiler control unit Function description External extensions accessories 5773 216 GB Functions ...

Page 125: ... pump sÖ 33 1 delivered condition 34 1 Circulation pump for cylinder heating sA 33 2 34 2 EA1 extension Fig 83 F1 MCB fuse DE1 Digital input 1 DE2 Digital input 2 DE3 Digital input 3 0 10V 0 10 V input fÖ Power supply fÖ A Power supply for additional accessories Function description External extensions accessories cont 5773 216 GB Functions ...

Page 126: ...cted in coding address 3E in the General group The effect on the relevant heating circuit pump is selected in coding address d6 in the Heating circuit group The effect on a circulation pump for cylinder heating is selected in coding address 5E in the DHW group Effect of the external demand function on the pumps The effect on the internal circulation pump is selected in coding address 3F in the Gen...

Page 127: ...over Code Changeover towards Continually reduced or Continuous standby mode subject to the selected set value d5 0 Changeover towards Continuous heating mode d5 1 The duration of the operating program changeover is set in coding address F2 in the Heating circuit group Heating program changeover Code No operating program changeover F2 0 Duration of the operating program changeover 1 to 12 hours F2 ...

Page 128: ...he burner is switched off during the venting program Activating the venting program See Venting the heat ing system Fill program In the delivered condition the diverter valve is set to its central position enabling the system to be filled com pletely After the control unit has been switched on the diverter valve no longer goes into its central position Afterwards the diverter valve can be moved in...

Page 129: ...e or after the control unit has been switched off Heating and DHW is started when screed drying is finished or if code F1 0 is set manually Temperature profile 1 EN 1264 4 code F1 1 Flow temperature C 1 5 10 15 20 25 30 Days 50 40 30 20 10 Fig 84 Temperature profile 2 ZV parquet and flooring technology code F1 2 Flow temperature C Days 50 40 30 20 10 1 5 10 15 20 25 30 Fig 85 Temperature profile 3...

Page 130: ...0 Raising the reduced room temperature During operation at reduced room temperature the reduced set room temperature can be automatically raised subject to the outside temperature The temper ature is raised in accordance with the selected heating curve and no higher than the set standard room tem perature The outside temperature limits for the start and end of temperature raising can be set in cod...

Page 131: ...ature Reducing the heat up time During the transition from operation with reduced room temperature to operation with standard room tempera ture the boiler water or flow temperature is raised in accordance with the selected heating curve The boiler water or flow temperature increase can be automati cally raised The value and duration for the additional increase of the set boiler water or flow tempe...

Page 132: ...he heating circuit allocation must be configured when commissioning the Vitotrol Heating circuit Vitotrol configuration 200A 200 RF 300A 300 RF The remote control affects the heating circuit without mixer A1 H 1 HC 1 The remote control affects the heating circuit with mixer M2 H 2 HC 2 The remote control affects the heating circuit with mixer M3 H 3 HC 3 Note One heating circuit can be assigned to...

Page 133: ...hip between the CO2 or O2 content and air ratio λ is illustrated in the following table Air ratio λ CO2 O2 content Air ratio λ O2 content CO2 content for natural gas E CO2 content for natural gas LL CO2 content for LPG P 1 20 3 8 9 6 9 2 11 3 1 24 4 4 9 2 9 1 10 9 1 27 4 9 9 0 8 9 10 6 1 30 5 3 8 7 8 6 10 3 1 34 5 7 8 5 8 4 10 0 1 37 6 1 8 3 8 2 9 8 1 40 6 5 8 1 8 0 9 6 1 44 6 9 7 8 7 7 9 3 1 48 7...

Page 134: ... temperature sensor aA Ionisation electrode aG Flue gas temperature sensor dÖ Stepper motor for diverter valve fJ Temperature limiter gF Ignition unit a Ö Fan motor a ÖA Fan motor control a Ö Modulation coil Connection and wiring diagram Internal connection diagram 5773 216 GB Appendix ...

Page 135: ...Electrical interfaces Outside temperature sensor Flow temperature sensor low loss header Cylinder temperature sensor plug on cable har ness sÖ Internal circulation pump sA Cylinder loading pump sK DHW circulation pump dG Gas solenoid valve fÖ Power supply lH Power supply for accessories and Vitotrol 100 a Ö Fan motor a ÖA Fan motor control aYA Gas pressure switch aVG KM BUS Connection and wiring d...

Page 136: ... type Carbon dioxide content CO2 For natural gas At lower heating output by vol 7 5 9 5 At upper heating output by vol 7 5 9 5 For LPG At lower heating output by vol 8 8 11 1 At upper heating output by vol 8 8 11 1 Oxygen content O2 At lower heating output by vol 4 0 7 6 At upper heating output by vol 4 0 7 6 Carbon monoxide content CO At lower heating output ppm 1000 At upper heating output ppm 1...

Page 137: ...ter setting C 81 Temperature limiter setting fixed C 100 Weight kg 129 129 132 141 Supply values relative to the max load Natural gas E m3 h 1 89 1 89 3 23 3 69 Natural gas LL m3 h 2 20 2 20 3 75 4 30 LPG P kg h 1 40 1 40 2 38 2 73 Permissible ambient temperature During operation C 0 to 40 During storage and trans port C 20 to 65 IP rating IP X 4 D to EN 60529 Protection class I Product ID CE 0085...

Page 138: ...wer supply and allow components to cool down where appropriate All components must be disposed of correctly DE We recommend using the disposal system organ ised by Viessmann Operating fluids e g heat transfer medium can be disposed of at municipal collection points Viessmann sales offices can provide further information Disposal Final decommissioning and disposal 5773 216 GB Appendix ...

Page 139: ...EC 811 2013 2006 95 EC 813 2013 2009 142 EC This product meets the requirements of the Efficiency Directive 92 42 EEC for condensing boilers Allendorf 01 October 2015 Viessmann Werke GmbH Co KG Authorised signatory Manfred Sommer Manufacturer s certificate according to the 1st BImSchV Germany We Viessmann Werke GmbH Co KG D 35107 Allendorf confirm that the product Vitodens 222 F type B2TA complies...

Page 140: ...27 External demand 128 F Fault codes 82 Fault history 81 Fault manager 52 Fault memory 81 82 Fault messages calling up 81 Faults 81 Fill function 128 Fill water 26 Flow temperature sensor 92 Flue gas temperature sensor 94 Function descriptions 120 Function testing 79 Fuse MCB 96 G Gas supply pressure 32 Gas train 32 Gas type 31 Gas type conversion 31 H Heating circuit allocation 132 Heating curve ...

Page 141: ...ure selection 51 Setting heating output 34 Setting the time 28 Siphon 37 Specification 137 Standard set room temperature 51 Static pressure 32 Supply pressure 32 System filling 27 System pressure 27 System schemes 46 55 System version 46 T Temperature limiter 95 Tightness test balanced flue system 34 V Venting 29 Venting program 128 Vitotronic 200 H 98 W Wiring diagram 134 Keyword index Keyword in...

Page 142: ...142 5773 216 GB ...

Page 143: ...143 5773 216 GB ...

Page 144: ...ited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke GmbH Co KG D 35107 Allendorf Telephone 49 6452 70 0 Fax 49 6452 70 2780 www viessmann com 5773 216 GB Subject to technical modifications ...

Reviews: