Vitotronic 100, KW10B Operating and User’s Information
Diagnostics
Operation
Failure, cause, correction
o
Are all controls operating properly (i.e. thermostats,
low water cut-off, etc.)?
o
Are all wire connections tight and secure?
Symptom/Condition
Cause
Correction
Boiler control is not active
(GREEN power LED is not illuminated)
Power switch “
8
“ is in “
0
“ position
Ensure power switch “
8
“ is in “
I
“
position.
Main power to boiler control and
heating system has not been
activated
Activate main power; ensure
120 VAC is supplied to control
(receptacle).
Fuse on Vitotronic boiler control has
deactivated heating system
Replace fuse in control with same
type and rating
(F1: T 6.3 A / 250 V, slow blow).
Burner does not activate, or activates
intermittently
(RED fault LED flashes)
Burner is not electrically connected
Ensure 7-pole
fA
plug-in connection
to burner and/or power venter is/are
made.
Fixed high limit (FHL) tripped
Reset FHL by pushing in the pin,
labelled with a “
E
“ (using a
ballpoint pen).
If a “click” can be heard, the limit
was tripped.
No fuel
*
1
with oil:
Ensure sufficient supply of oil
with gas:
Open main gas supply valve
or
contact your local gas utility
Pumps on continuously
F1 fuse blown
Replace fuse
Burner does not activate
Control calls for heat but burner does
not respond
*
1
Attempt to reset burner using reset
button on the burner
(underneath burner hood).
Service burner if necessary.
Refer to troubleshooting section in
burner manual.
Control calls for heat but burner does
not respond
Power venter has to have separate
120 VAC power supply to motor (see
power venter instructions).
Refer to troubleshooting section in
power venter manual. Air proving
switch, blower wheel or timer/relay
inside power vent may be defective.
Other accessory defect
Ensure proper operation of all
accessories; replace if necessary.
Refer to technical literature supplied
with accessories.
F1 fuse blown
Replace fuse
Continuous burner call
F3 Fuse blown
Replace fuse
Override switch on
Turn off override
*
1
Red LED does not flash when Honeywell S8600 ignition control module is used with boiler.