7.4.3 Relay connection
Relays can be used for low working
voltages only (up to 30Vac or 60Vdc) and
with a maximum current of 1A. Use cables
with a section suitable for the load to be
controlled and use cables with a minimum
section of 0.25mm² (AWG 24) and maximum
section of 1.5mm² (AWG 16).
The R1A, R1B, R2A and R2B relay clamps are located
in the J4 connector. Relays do not have polarity and
therefore both terminals A or B of the same relay
can be used, for alternating or continuous current
voltages.
RELAY CONNECTION
Terminal
Description
R1A
Relay 1, Terminal A
R1B
Relay 1, Terminal B
R2A
Relay 2, Terminal A
R2B
Relay 2, Terminal B
Tab.
6
For further information refer to the relative
chapter (9.1.12.1 Alarms Menu, page 42).
7.4.4 Connecting the light sensitive
switch for the LED illuminator
During installation do not look directly at
the illuminator while it is on.
To guarantee correct vision during the day
and the night, it is necessary to correctly set
the sensor.
The light sensitive switch must be
positioned so that it is not hit by the light
beam coming from the illuminator or by
artificial lights (such as road lights, car
headlights, etc.).
Fig.
20
Summary of Contents for ULISSE COMPACT
Page 2: ......
Page 4: ......
Page 83: ......
Page 86: ......
Page 165: ......
Page 168: ......
Page 247: ......
Page 250: ......
Page 329: ......
Page 331: ...RU ULISSE COMPACT PTZ...
Page 332: ......
Page 339: ...RU 9 MNVCUCZ_1511_RU 10 UPS 6 12...
Page 342: ...RU 12 MNVCUCZ_1511_RU 6 6 1 6 6 2 6 3 IP 6 4...
Page 381: ...RU 51 MNVCUCZ_1511_RU 9 3 8 Preset Parametri Preset autopan patrol preset 109 9 3 9 Preset 110...
Page 384: ...RU 54 MNVCUCZ_1511_RU 10 10 1 115 9 1 13 43 10 2 116 10 3 117 10 4 118 9 1 12 41...
Page 392: ...RU 62 MNVCUCZ_1511_RU 13 14 preset...
Page 397: ...RU 67 MNVCUCZ_1511_RU 16 124 387 274 349 261 123 ULISSE COMPACT...
Page 398: ...RU 68 MNVCUCZ_1511_RU 124 390 274 349 391 261 124 ULISSE COMPACT LED...
Page 411: ......
Page 413: ......