1.5 XTENDER Mode configuration
5
W Panel
www.videofied.com
WIO 100 Input/Outputs module
ARMING PROFILE :
FROM THE HOST
When a WIO100 Input/outputs module is fitted on the W panel, the XTENDER mode can be configured either during
initial configuration, or in the GENERAL PARAMETERS menu.
• During initial configuration,
the ARMING PROFILE screen will appear.
Choos FROM THE HOST instead of STANDALONE to access the XTENDER
mode configuration menu.
• Access the configuration menu
from the GENERAL PARAMETERS menu :
CONFIGURATION (Lvl 4) > GENERAL PARAMETERS > XTENDER
MODE SLOW
: The panel will arm each device one at a
time saving battery life. This mode is recommended.
MODE FAST
: The panel will arm all devices
at the same time. This mode increases
significantly the battery consumption.
Press
OK
or
YES
to select the parameter.
Enter the value for your Entry Delay up to 255 seconds
and press
OK
or
YES
.
Note : In From the Host mode, the entry/exit delay are
managed by the master system.
Arming Confirmation is the number of seconds the
system will wait to arm after voltage is latched on the
arming input. This feature can be used as an exit delay,
we suggest you to enter the same value as your master
system exit delay.
Enter the value you would like for the Arming
Confirmation and press
OK
or
YES
.
ARMING PROFILE :
FROM THE HOST
ENTRY DELAY
VALUE (0-255) :
(000) : _
TRANSMISSION DELAY
VALUE (0-600) :
(000) : _
ARMING CONFIRMATION
VALUE (0-240) :
(0) : _
OK
or
YES
ARMING MODE
MODE :
SLOW
MODE :
FAST
OK
or
YES
OK
or
YES
OK
or
YES
The transmission delay value set the delay between
the detection of an event and its transmission to the
monitoring center.
Except when specifically required, please enter 0.
Enter the value you would like for the Transmission Delay
and press
OK
or
YES
.
A P P L I C A T I O N N O T E