2022-03-05 21:27 3/14

Victron & Pylontech UP2500, US2000, US3000, US2000C, US3000C, UP5000, Phantom-S, Force-L1 & L2

Victron Energy - https://www.victronenergy.com/live/

Old model VE.Can MPPTs (pre 2019) are not supported.

2. Minimum Battery Sizing Recommendations

Once DVCC is enabled on the GX device, the charge and discharge rates are managed by the
Pylontech battery.

Using very large solar arrays with battery banks that are too small can exceed the limits of the
batteries ability to charge and possibly lead to the BMS triggering over-current alarms.

You must have the minimum number of battery modules to supply the inverters startup inrush surge
currents that charge the capacitors when the inverter is first connected, this occurs prior to any loads
being connected. There is also the subsequent potential current demands of the loads connected to
the inverter. It is much more desirable to have the inverter/charger overload than the battery, as the
inverter will automatically recover, whereas the battery may require intervention once in a fault state.

Some suggested battery sizings for common Victron inverter/chargers are listed below. These are
suggestions for reliable operation for single phase off grid and are not specified by Pylontech.

Using the above formula, an example of minimum system sizing based on the US2000 battery module
is below. Each battery module is approximately 50Ah at 48V, can provide 25A continuous charge and
discharge and 100A peak for 1 minute.

Inverter / Charger Model

Inv
continuous
watts @ 25
degrees

Inverter
peak
watts
surge
rating

Number of
Pylontech
modules

Battery
continuous
discharge
watt rating

Battery
peak
discharge
watt rating

Multiplus 48/500/6

430

900

1

1200

4800

Multiplus 48/800/9

700

1600

1

1200

4800

Multiplus 48/1200/13

1000

2400

1

1200

4800

Multiplus 48/3000/35

2400

6000

2

2400

9600

Multiplus 48/5000/70

4000

10000

4

4800

19200

Quattro 48/8000/110-100/100 6500

16000

6

7200

28800

Quattro
48/10000/140-100/100

8000

20000

7

8400

33600

Quattro
48/15000/200-100/100

12000

25000

10

12000

48000

3. CAN-bus Wiring

Summary of Contents for Pylontech Force-L1

Page 1: ...ing integration with Victron systems The Pylontech includes a Battery Management System BMS with each battery module This interfaces with the Victron GX device and can support multiple battery modules connected in parallel 1 Product system compatibility Battery UP2500 US2000 Plus C US3000 C UP5000 Force L1 L2 Nominal voltage 24V 48V 48V 48V 48V Module capacity 2 55 kWh 2 4 kWh 3 5 kWh 4 8 kwh 3 55...

Page 2: ...commended where possible and a necessary first step when troubleshooting issues These inverter charger units must be connected to the GX device via the VE Bus connection port Legacy systems installed with VE Bus firmware 422 can continue to be used without upgrade as long as they do not present any issues 1 4 All VE Direct BlueSolar and SmartSolar MPPT Chargers are compatible For proper operation th...

Page 3: ...he battery as the inverter will automatically recover whereas the battery may require intervention once in a fault state Some suggested battery sizings for common Victron inverter chargers are listed below These are suggestions for reliable operation for single phase off grid and are not specified by Pylontech Using the above formula an example of minimum system sizing based on the US2000 battery mo...

Page 4: ... documentation for more details The batteries will automatically detect and link to each other no adjustment of dip switches on the battery module are necessary The battery with the empty link port 0 is the master battery You must use the VE Can to CAN bus BMS type B Cable part number ASS030720018 for connection with US2000 US3000 UP2500 and VE Can to CAN bus BMS type A Cable part number ASS030710...

Page 5: ...be connected to this If you connect the BMS to the VE Can port you will need to adjust the port speed Select the CAN bus BMS 500 kbit s CAN profile in the GX device Menu path Settings Services VE CAN port After properly wiring and setting the correct CAN bus speed the Pylontech will be visible as a battery in the device list If you have multiple batteries a single entry will show up which represent...

Page 6: ...es could potentially absorb more The parameters option within the battery page shows the battery charge and discharge limits as communicated to the DVCC system by the BMS The charge current limit CCL as shown in the parameters screen and received from the BMS by the GX device via DVCC will be the ceiling and the system will try its best not to exceed that as much as it can it may spike under momen...

Page 7: ...his section presumes familiarity with VEConfigure software Voltages shown are for the 48V model and should be scaled for the 24V model The 24V model is an 8 series configuration while the 48V model is a 15 series configuration Voltages should therefore be scaled by 8 15 5 1 General tab Check the Enable battery monitor function Set the battery capacity to the total capacity of the battery eg 50Ah time...

Page 8: ...system please review the ESS Quickstart guide and Design and Installation Manual The settings that are specific to the Pylontech battery in the VEConfigure ESS Assistant are below Select the externally managed Lithium battery option ESS Parameter Settings Sustain voltage 48V Dynamic cut off values set all values to 46V Restart offset 1 2V Default Due to the reliability of the grid supply and the behav...

Page 9: ...charge Current Limit set to 0A at 47V inverter will turn off Over charge and Over discharge Current Limit 102A for 15 seconds 200A for 0 1 seconds and 400A short circuit current If operation is attempted outside the operating range the battery will disconnect to protect itself 6 VE Direct MPPT Settings In normal operation the MPPT charge characteristics are governed by the GX device via DVCC with i...

Page 10: ...shooting If the system is not operating correctly go through these steps Step 0 If the Inverter Charger or GX device does not switch on As a safety precaution the inverter charger will not switch on if the GX device is not on If you are unable to start the system due to a total system blackout battery shutdown due to low voltage you may need to disconnect the VE BUS connection cable between the in...

Page 11: ...ion v2 15 or later CAN bus communication cabling between Pylontech and Victron system Make sure that it is in the right way around Pylontech system is up and running LEDs are on Step 2 Check that the Pylontech battery is ready for use Check the Max Charge Voltage parameter This voltage parameter is sent together with the other three parameters by the Pylontech system via the CAN bus cable They are...

Page 12: ...on be entering the Pylontech Battery menu on your GX device and then the Parameters Menu This will report the Charge Current Limit CCL and Discharge Current Limit DCL This information is also logged in the advanced section of the VRM monitoring portal My system only charges the battery to 52 4V When DVCC is enabled the battery via the CAN bms is responsible for the charge voltage The Pylontech bat...

Page 13: ...re unable to maintain the target voltage to balance the batteries without the high voltage alarm occurring you may need to enable and set the Limit managed battery charge voltage setting in the DVCC menu of the GX device Reduce this voltage as necessary until the alarm stops After sufficient time to balance the batteries try increasing this value until it can be disabled again for normal operation I...

Page 14: ...ve Printed on 2022 03 05 21 27 Further community discussion about installing and using Pylontech and Victron can found at Victron Community use the topic label Pylontech DISQUS View the discussion thread From https www victronenergy com live Victron Energy Permanent link https www victronenergy com live battery_compatibility pylontech_phantom rev 1618822856 Last update 2021 04 19 11 00 ...

Reviews: