VEConfigure Inverter Parameter Setting
DC input low shut-down
44V
DC input low restart
48V
DC input low pre-alarm*
48V
* The pre-alarm setting is dependant on your preference and on site specific requirements. You may
wish for this to be activated earlier in an off grid situation to allow time to start a backup generator.
ESS System Settings
If you are using the battery as part of a
and
Design and Installation Manual
.
The settings that are specific to the Pylontech battery in the VEConfigure ESS Assistant are below:
Select the externally managed Lithium battery option
ESS Parameter
Settings
Sustain voltage.
48V
Dynamic cut-off values set all values to 46V.
Restart offset:
1.2V (Default)
Due to the reliability of the grid supply and the behaviour of the sustain voltage threshold in ESS; you
may wish to suppress the low voltage pre-alarm warning so that it does not trigger every day on its
regular deep cycle. See
- about suppressing the low-voltage alarm.
Hardware Protection Points
In normal operation, the charge parameter limits are set by the Pylontech battery and communicated
through the system by the