You can connect multiple battery modules together to form a single large battery by connecting the
RJ-45 cable supplied by Pylontech using the link ports on the battery. This is shown in more detail in
the
and Pylontech manual.
The communications for UP2500 can be paralleled up to 20 modules per string (and cannot use the
LV-HUB). Other models can connect up to 8 battery modules (see Pylontech data sheets), in those
models when using more than 8 parallel units, some limitations, additional configuration or equipment
(e.g. Pylontech LV-Hub) may apply. See your Pylontech dealer, and Pylontech documentation for more
details.
The batteries will automatically detect and link to each other, no adjustment of dip switches on the
battery module are necessary.
The battery with the empty link port 0 is the master battery. You must use the VE.Can to CAN-bus
BMS type B Cable, part number ASS030720018 for connection with US2000/US3000/UP2500; and
VE.Can to CAN-bus BMS type A Cable, part number ASS030710018 for connection with
US2000C/US3000C/UP5000/Force-L, you cannot use the cable supplied by Pylontech.
Plug the communication cable with the side which is labeled Battery BMS into the Pylontech CAN port
of the master battery.
Some GX devices (such as the Cerbo GX), have multiple CAN ports. If your GX device has a BMS-Can
port, this should be used. If your GX device ONLY has VE.Can ports, you will need to this for the
battery (and then it cannot be used for other VE.Can devices).
Plug the side labeled Victron VE.Can into the
in the other VE.Can socket on the