20
Phoenix Inverter
24/5000
48/5000
INVERTER
Input voltage range (V DC)
19 – 33
38 – 66
Output
(1)
Output voltage: 230 VAC ± 2% Frequency
:
50 Hz ± 0,1%
Cont. output power at 25°C (VA)
(3)
5000
5000
Cont. output power at 25°C (W)
4000
4000
Cont. output power at 40°C (W)
3700
3700
Cont. output power at 65°C (W)
3000
3000
Peak power (W)
10000
10000
Maximum efficiency (%)
94
95
Zero-load power (W)
30
30
GENERAL
Programmable relay
(4)
Yes
Yes
Protection
(2)
a - g
Common Characteristics
Operating temp.: -40 to +65°C (fan assisted cooling)
Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics
Material & Colour: aluminium (blue RAL 5012) Protection: IP 21
Battery-connection
M8 bolts (2 plus and 2 minus connections)
230 V AC-connection
Screw clamp 13mm² (6 AWG)
Weight (kg)
30
Dimensions (hxwxd)
444 x 328 x 240
STANDARDS
Safety
EN 60335-1, EN 60335-2-29
Emission / Immunity
EN 55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3
1) Can be adjusted to 60Hz; 120V/60Hz on request
2)
Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) Multipurpose relay which can be set for general alarm, DC undervoltage or genset start signal
function