14
3.6.2 Temperature Sensor (Multi Compact / MultiPlus Compact)
The temperature sensor supplied with the product may be used for temperature-
compensated charging. The sensor is insulated and must be mounted on the batteries minus
pole. Default output voltages for Float and Absorption are at 25°C. In adjust mode
temperature compensation is disabled.
10.0
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
14.5
15.0
0
5
10
15
20
25
30
35
40
45
50
55
60
Battery temperature
Volts
20
21
22
23
24
25
26
27
28
29
30
Volts
3.6.3 Remote Control panel & remote on/off switch
The product can be operated remotely in two ways.
Use of only an external switch.
With the aid of a remote control panel.
Observe the following when using only an external switch:
Only functions if the switch on the product is switched to the "on" position.
Not to be connected if a remote control is connected.
Observe the following when using a remote control:
Only functions if the switch on the product is switched to the "on" position.
3.6.4 External Alarm Relay and Virtual Switch
An open collector output is available to connect a relay that can be used for remote alarm and
other purposes (a. o. generator start signal).The maximum voltage/current that can be
switched (open collector transistor): 66V 40mA.
The open collector output can be programmed with VEConfigure.
Summary of Contents for Phoenix 12/1200
Page 3: ......
Page 57: ...28 ...
Page 84: ...27 GB NL F D Appendix ...
Page 85: ......
Page 115: ...30 ...
Page 116: ...1 GB NL F D Appendix ...
Page 117: ...2 ...
Page 118: ...3 GB NL F D Appendix ...
Page 119: ...4 ...
Page 120: ...5 GB NL F D Appendix ...
Page 121: ...6 ...
Page 122: ...7 GB NL F D Appendix ...
Page 123: ......