11
GB
NL
F
D
Appe
ndix
3.3 Requirements
Philips screwdriver (PH2) for removing the front.
Flat screwdriver (0.6x3.5) for connecting the AC leads.
Three-wire cable.
3.4 Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
24/800
24/1200
12/800
12/1200
12/1600
48/1600
24/1600
48/1200
Recommended
cross section (mm
2
)
1,5
1
Æ
5
m
16 25 35 50 70
5
Æ
10 m
35
50
70
100
140
1) preassembled cable length: 1.5 m
24/800
24/1200
12/800
12/1200
12/1600
48/1600
24/1600
48/1200
Recommended
battery capacity (Ah)
40 – 200
40 – 400
100 – 400
150 – 700
200 – 700
Remark: Internal resistance is the important factor when working with low capacity batteries.
Please consult your supplier or the relevant sections of our book “electricity on board”,
downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect the battery cables: the + (red) on the left and the - (black) on the right, to the battery
see Anhang A.
Reverse polarity connection (+ to – and – to +) will cause damage to the Phoenix Multi
Compact.(Safety fuse inside the Multi Compact can be damaged)
Secure the nuts tightly in order to reduce the contact resistance as much as possible.
Summary of Contents for Phoenix 12/1200
Page 3: ......
Page 57: ...28 ...
Page 84: ...27 GB NL F D Appendix ...
Page 85: ......
Page 115: ...30 ...
Page 116: ...1 GB NL F D Appendix ...
Page 117: ...2 ...
Page 118: ...3 GB NL F D Appendix ...
Page 119: ...4 ...
Page 120: ...5 GB NL F D Appendix ...
Page 121: ...6 ...
Page 122: ...7 GB NL F D Appendix ...
Page 123: ......