4 FIRST POWER UP
Other than below procedure, no configuration is needed. The battery configuration is automatically recognized.
4.1 Power up procedure
1.
Make sure that all energy consumers are switched off before starting up the system, because the Lynx Ion BMS will
pre-charge the system before closing the safety contactor.
2.
Press the START-button (green button) on the front of the Lynx Ion BMS to start the system.
3.
The system is pre-charging now. The safety contactor is closed as soon as the voltage rises above 80% of the
battery voltage.
4.
If the status LED is continuously on, the system is running and ready for use.
The Lynx Ion BMS will not start if there is more than 10A drawn by the system during pre-charging. A
pre-charge error will be given and the Lynx Ion BMS will go to fail-safe.
During start-up of the system it is possible that The Lynx Ion BMS will going to update the battery
firmware if necessary. This is an automatic process and may not be interrupted.
4.2 Power down/reset procedure
Lynx Ion BMS to standby mode:
1.
Press and hold the START-button until the Lynx Ion BMS goes into standby mode (status LED off).
2.
Now the safety contactor is open and the batteries are disconnected from the system.
Reset Lynx Ion BMS from fail safe state:
1.
Press the START-button for 1 second.
2.
The system will now restart.
4.3 Automatic power-up
The Lynx Ion BMS will automatically power-up from standby if a charge voltage is supplied on the output for more than 10
seconds.