5 CONNECTING A VICTRON MULTI OR QUATTRO
5.1 Connection of a Multi or Quattro inverter/charger
The Multi and Quattro needs to stop charging when the batteries are fully charged and stop discharging when the batteries are
empty. To achieve this the allow-to-charge and allow-to-discharge signal contacts of the Lynx Ion BMS are used.
See the switching boundaries document for details about the switching levels for your specific battery.
5.2 Connecting the allow-to-charge and allow-to-discharge
5.2.1 Connecting 1 Multi or Quattro
Below an example of how to connect one Multi or Quattro to the Lynx Ion BMS.
To use the Quattro/Multi in combination with the Lynx Ion BMS, there must be an assistant configured. If
the assistant is configured properly, the allow-to-charge and allow-to-discharge contacts are enabled.
Lynx-ion BMS
Summary of Contents for Lynx Ion BMS 1000A