Figure 6. Correct mounting sequence DC wires
M8 bolt
M8 Spring washer
M8 Washer
Cable lug
Lynx module
Correct placement of the M8 Cable lug, washer, spring washer and nut
6.2.3. Ground and Negative connections
Connect the ground wire
This only applies if the system requires a ground connection. There should only be one ground connection per system. The
ground connection should be made after the Lynx Smart BMS, Lynx Shunt VE.Can or battery monitor shunt. For more information
on system grounding see the
.
The ground connection of the Lynx Distributor has a wire with red cable lug already connected to it. Leave this wire in place when
connecting the ground wire.
Leave the red
wire in place
Ground connection Lynx Distributor
Connect the negative wires
Remove the cable separator post if the wire diameter exceeds 10mm.
The cable separator posts are indicated in yellow
To reach the negative connections swing the black cable separators upwards. The black cable separators can be temporary
removed by pulling them away from the Lynx Distributor at a slight sideways angle in case better access is needed.
Lynx Distributor