6. Installation
6.1. Mechanical connections
6.1.1. Lynx module connection features
The Lynx module can be opened up by unscrewing 2 cover screws.
The contacts on the left side are covered by a removable rubber sleeve.
Red is the positive busbar and black is the negative busbar.
Cover
screw
Cover
screw
Removable sleeve
Positive busbar
Removable sleeve
Negative busbar
Location of front cover screws and the removable sleeves
6.1.2. Mounting and interconnecting Lynx modules
This paragraph explains how to attach several Lynx modules to each other and how to mount the Lynx assembly into its final
location.
For a mechanical drawing of the housing, with dimensions and the location of the mounting holes, see the appendix of this
manual.
These are the points to take into consideration when interconnecting and mounting Lynx modules:
• If Lynx modules are going to be connected to the right and if the Lynx module is fitted with a plastic barrier on the right side,
remove the black plastic barrier. If the Lynx module is located as the most right module, leave the black plastic barrier in place.
• If Lynx modules are going to be connected to the left, remove the red and black rubber sleeves. If the Lynx module is located
as the most left module, leave the red and black rubber sleeves in place.
• If the Lynx system contains a Lynx Smart BMS or Lynx Shunt VE.Can, the left side is the battery side and the right side is the
DC system side.
• Connect all Lynx modules to each other using the M8 holes and bolts on the left and right. Take care that the modules correctly
slot into the rubber joiner recesses.
• Place the washer, spring washer and nut on the bolts and tighten the bolts using a torque of 14Nm.
• Mount the Lynx assembly in its final location using the 5mm mounting holes.
Lynx Distributor
Page 12
Installation