6. MAINTENANCE
The Phoenix Inverter does not require specific maintenance. It will suffice to check all
connections once a year. Avoid moisture and oil/soot/vapours, and keep the device
clean.
7. FAULT INDICATIONS
With the procedures below, most errors can be quickly identified. If an error cannot be
resolved, please refer to your Victron Energy supplier.
7.1 General error indications
Problem
Cause
Solution
Inverter operation not
initiated when
switched on.
The battery voltage is excessively
high or too low. No voltage on DC
connection.
Ensure that the battery voltage is
within the correct range.
“Low battery” LED
flashes.
The battery voltage is low.
Charge the battery or check the
battery connections.
“Low battery” LED
lights.
The converter switches off
because the battery voltage is too
low.
Charge the battery or check the
battery connections.
“Overload” LED
flashes.
The converter load is higher than
the nominal load.
Reduce the load.
“Overload” LED
lights.
The converter is switched off due
to excessively high load.
Reduce the load.
“Temperature” LED
flashes or lights.
The environmental temperature is
high, or the load is too high.
Install the converter in cool and
well-ventilated environment, or
reduce the load.
“Low battery” and
“overload” LEDs
flash intermittently.
Low battery voltage and
excessively high load.
Charge the batteries, disconnect
or reduce the load, or install
higher capacity batteries. Fit
shorter and/or thicker battery
cables.
“Low battery” and
“overload” LEDs
flash simultaneously.
Ripple voltage on the DC
connection exceeds 1,5Vrms.
Check the battery cables and
battery connections. Check
whether battery capacity is
sufficiently high, and increase
this if necessary.
“Low battery” and
“overload” LEDs
light.
The inverter is switched off due to
an excessively high ripple voltage
on the input.
Install batteries with a larger
capacity. Fit shorter and/or
thicker battery cables, and reset
the inverter (switch off, and then
on again).
One alarm LED lights
and the second
flashes.
The inverter is switched off due to
alarm activation by the lighted
LED. The flashing LED indicates
that the inverter was about to
switch off due to the related alarm.
Check this table for appropriate
measures in regard to this alarm
state.
Summary of Contents for 12 120V
Page 1: ...Manual EN Appendix Phoenix Inverter with firmware xxxx1xx 12 3000 120V 24 3000 120V ...
Page 2: ......
Page 4: ......
Page 25: ...EN Appendix APPENDIX B Block diagram See table in chapter 4 2 Recommended DC fuse ...
Page 26: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 27: ...EN Appendix APPENDIX G Dimensions ...
Page 28: ...Dimensions 3k cabinet ...
Page 29: ......