Setting ds2 and ds1 for parallel operation
Master
Slave 1
Slave 2 (optional)
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 AES
na
x
DS-4 Inv. voltage Set
DS-3 Inv. freq
Set
DS-2 Master
off
DS-1 Master
on
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 na
x
DS-3 na
x
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 na
x
DS-3 na
x
DS-2 Slave 2
off
DS-1 Slave 2
on
To store the settings after the required values have been set: press the 'Up' button of
the
master
for 2 seconds (
upper
button to the right of the DIP switches, see appendix
A, position J).
The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can
always be recovered.
Setting ds2 and ds1 for 3-phase operation
Leader (L1)
Follower (L2)
Follower (L3)
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 AES
na
x
DS-4 Inv. voltage Set
DS-3 Inv. freq
Set
DS-2 Leader
on
DS-1 Leader
off
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 Set
DS-3 na
x
DS-2 L2
off
DS-1 L2
off
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 Set
DS-3 na
x
DS-2 L3
off
DS-1 L3
on
As the table above shows, the Inverter voltage should be set separately (ds4) for
every Inverter
AES can be used on stand alone units only.
To store the settings after the required values have been set: press the 'Up' button of
the
Leader
for 2 seconds (
upper
button to the right of the DIP switches, see appendix
A, position J).
The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can
always be recovered.
To start the system: first, turn all devices off. The system will start up as soon
as all devices have been turned on.
Summary of Contents for 12 120V
Page 1: ...Manual EN Appendix Phoenix Inverter with firmware xxxx1xx 12 3000 120V 24 3000 120V ...
Page 2: ......
Page 4: ......
Page 25: ...EN Appendix APPENDIX B Block diagram See table in chapter 4 2 Recommended DC fuse ...
Page 26: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 27: ...EN Appendix APPENDIX G Dimensions ...
Page 28: ...Dimensions 3k cabinet ...
Page 29: ......