AUTO-CUT 200 XT
Manual 0-5253
INSTALLATION
3-7
4. The plasma power supply work cable (see NOTE) is connected to the cutting table at the single point “Star”
ground.
NOTE
Do Not connect the work cable directly to the ground rod.
5. Make sure work cable and ground cables are properly connected. The work cable must have a solid connec-
tion to the cutting table. The work and ground connections must be free from rust, dirt, grease, oil and paint. If
necessary grind or sand down to bare metal. Use lock washers to keep the connections tight. Using electrical
joint compound to prevent corrosion is also recommended.
6. The plasma power supply chassis is connected to the power distribution system ground as required by electrical
codes. If the plasma supply is close to the cutting table (see NOTE) a second ground rod is not usually needed,
in fact it could be detrimental as it can set up ground loop currents that cause interference.
When the plasma power supply is far away from the ground rod and interference is experienced, it may help to
install a second earth ground rod next to the plasma power supply. The plasma power supply chassis would
then be connected to this ground rod.
NOTE
It is recommended that the Plasma Power Supply be within 20 - 30 ft (6.1 – 9.1 m) of the cutting table,
if possible.
7. The plasma control cable should be shielded with the shield connected only at the cutting machine end. Con-
necting the shield at both ends will allow ground loop currents which may cause more interference than with no
shield at all.
C. Creating An Earth Ground
1. To create a solid, low resistance, earth ground, drive a 1/2 in (12 mm) or greater diameter copper clad ground
rod at least 6 - 8 ft (1.8 - 2.4 m) into the earth so that the rod contacts moist soil over most of its length. Depend
-
ing on location, a greater depth may be required to obtain a low resistance ground (see NOTE). Ground rods,
typically 10 ft (3.0 m) long, may be welded end to end for greater lengths. Locate the rod as close as possible
to the work table. Install a ground wire, 1/0 AWG (European 50 mm2) or greater, between the ground rod and
the star ground point on the cutting table.
NOTE
Ideally, a properly installed ground rod will have a resistance of three ohms or less.
Summary of Contents for Auto-Cut 200 XT
Page 4: ...This page intentionally blank...
Page 8: ...TABLE OF CONTENTS...
Page 48: ...AUTO CUT 200 XT INSTALLATION Manual 0 5253 This Page Intentionally Blank...
Page 66: ...This Page Intentionally Blank...
Page 97: ...AUTO CUT 200 XT Manual 0 5253 APPENDIX A 11 This Page Intentionally Blank...
Page 107: ...AUTO CUT 200 XT Manual 0 5253 APPENDIX A 21 Display PCB Test Points TP1 GND TP2 5VDC TP3 24VDC...
Page 116: ...AUTO CUT 200 XT APPENDIX Manual 0 5253 APPENDIX 12 CAP BIAS BOTTOM PCB LAYOUT Art A 11685...
Page 117: ...AUTO CUT 200 XT Manual 0 5253 APPENDIX A 31 APPENDIX 13 CAP BIAS TOP PCB LAYOUT Art A 11686...
Page 118: ...AUTO CUT 200 XT APPENDIX Manual 0 5253 APPENDIX 14 SUPPRESSOR PCB LAYOUT Art A 11684...
Page 121: ...AUTO CUT 200 XT Manual 0 5253 APPENDIX A 35 This Page Intentionally Blank...
Page 163: ...AUTO CUT 200 XT Manual 0 5253 APPENDIX A 77 This Page Intentionally Blank...
Page 165: ......