INSTRUCTIONS FOR INITIAL USE OF A VICTAULIC
®
FIRELOCK
™
NO. 101 90° ELBOW OR
NO. 102 STRAIGHT TEE INSTALLATION-READY
™
FITTING WITH A SERIES AH1-CC, AH2-CC, OR
AH2-CC-300 FLEXIBLE HOSE (1-INCH/DN25 IGS CONNECTION)
NOTICE
• The following procedure applies only to 1-inch/DN25 No. 101 90° Elbows and No. 102 Straight Tees (IGS connection).
• No. 101 90° Elbows and No. 102 Straight Tees do not ship preassembled to the Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible Hose.
• The No. 101 or No. 102 does not need to be fully disassembled for initial installation onto the inlet end of the Series AH1-CC, AH2-CC, or
AH2-CC-300 Flexible Hose.
1.
Loosen the nut of the Style 108 Coupling. Remove the Style 108 Coupling from the end of the Series
AH1-CC, AH2-CC, or AH2-CC-300 Flexible Hose.
Spacer
Inspect
Inlet End
of Flexible Hose
2.
Inspect the inlet end of the Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible Hose to verify that there is no
damage (dents, crushed edges, etc.). A new, Victaulic-supplied Series AH1-CC, AH2-CC, or AH2-CC-300
Flexible Hose shall be used if any damage is present.
3.
Verify that the spacer is oriented on the inlet end of the Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible
Hose, as shown to the left.
4.
Loosen and remove the hardware from the side of the No. 101 90° Elbow or No. 102 Straight Tee that is intended to connect with the inlet of the
Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible Hose.
NO. 101
NO. 102
5.
Insert the inlet end of the Series AH1-CC, AH2-CC, or AH2-CC-300
Flexible Hose into the No. 101 90° Elbow or No. 102 Straight Tee.
Verify that the gasket is seated fully in the gasket pocket of each
housing and that the housings' keys engage with the spacer on the
inlet end of the Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible
Hose.
5a.
Reinstall the two bolts and nuts that were removed in step 4.
NOTE:
Verify that the oval neck of each bolt seats properly in the bolt
holes. DO NOT tighten the nuts completely. The bolt pads need to
be set at a gap for installation of the fitting. The nuts should be flush
with the top of each bolt to provide the proper gap. Use caution when
handling the fitting/hose assembly (the fitting may not be secured
completely to the inlet end of the Series AH1-CC, AH2-CC, or
AH2-CC-300 Flexible Hose).
6.
Follow the steps in the I-101/103 or I-102/104 installation instructions for the required tightening sequence.
NOTE:
During tightening, verify
that the inlet end of the Series AH1-CC, AH2-CC, or AH2-CC-300 Flexible Hose remains straight and aligned with the opening of the No. 101
90° Elbow or No. 102 Straight Tee. The I-101/103 or I-102/104 can be accessed and downloaded by scanning the applicable QR code below. In
addition, these instructions contain important reassembly instructions and shall be referenced any time a No. 101 90° Elbow or No. 102 Straight
Tee is removed from the sprinkler piping and reused.
SCAN QR CODE FOR ACCESS TO THE FULL I-101/103
INSTALLATION INSTRUCTIONS ON VICTAULIC.COM
SCAN QR CODE FOR ACCESS TO THE FULL I-102/104
INSTALLATION INSTRUCTIONS ON VICTAULIC.COM