CntrlTyp

 

Control type for Triac models 
Default is: 

Floating

 

Defines the type of control output for the type of valves installed 

VT7350C10xx, VT7300C10xx, VT7355C10xx and VT7305C10xx only 
On/Off

 is for normally opened or normally closed 24 Vac 2 position valves 

 

Floating

 is for modulating 3 wires control of 24 Vac floating valves 

SeqOpera

 Sequence of operation 

Default is: 

Sequence #1

 

System = 2 Pipes 

System = 4 Pipes 

0 = Cooling Only 

Yes access 

Yes access 

1 = Heating only 

Yes access 

Yes access 

2 = Cooling With Reheat 

Yes access 

Yes access 

3 = Heating With Reheat 

Yes access 

Yes access 

4 = Cooling / Heating 4 pipes 

No access 

Yes access 

5 = Cooling / Heating 4 pipes with 
Reheat 

No access 

Yes access 

 

For single output applications, the system access is also limited if UI3 is configured 
for local changeover COS, COC/NC or COC/NC. The system mode available for 
the local configuration or network write is then limited by the current water 
temperature detected by the UI3. 

Fan Menu

 

Mode button menu configuration 
Default is: 

Menu #4

 

Menu presented are dependent on model used and sequence of operation 
selected 

0 = Low-Med-High 

3

 Speed configuration using 3 fan relays ( L-M-H ) 

1 = Low-High 

2

 Speed configuration using 2 fan relays ( L-H ) 

2 = Low-Med-High-Auto 

3

 Speed configuration with Auto fan speed mode using 3 fan relays ( L-M-H ) 

3 = Low-High-Auto 

2

 Speed configuration with Auto fan speed mode using 2 fan relays ( L-H ) 

4 = On-Auto 

Single

 Speed configuration. Auto is for Fan on demand / On is On all the time 

DHumiLCK

 

Dehumidification lockout 

VT735xX5x00(x) models only

 

Default value: 

On = Authorized

 

Typically toggled through the network. 
This variable enables or disables dehumidification based on central network 
requirements from the BAS front end 

On = 

Dehumidification Authorized 

Off = 

Dehumidification Not Authorized 

%RH set

 

Dehumidification setpoint 
Default is 

50 % RH

 

Used only if dehumidification sequence is enabled: 
Range is: 

30-95% RH  

VT735xX5x00(x) models only 

DehuHyst

 

Dehumidification Hysterisys 
Default is 

5 % RH

 

Humidity control hysterisys. Used only if dehumidification sequence is enabled: 

 

Range is: 

2 to 20% RH 

VT735xX5x00(x) models only

 

DehuCool

 

Maximum Dehumidification 
Cooling output 
Default is 

100 %  

Maximum cooling valve position when dehumidification is enabled. This can be 
used to balance smaller reheat loads installed in regards to the capacity of the 
cooling coil. 
Range is: 

20 to 100 %  

VT735xX5x00(x) models only

 

St-By TM 

Stand-by Timer value 
Default 

0.5 hours

 

Time delay between the moment where the PIR cover detected the last movement 
in the area and the time which the thermostat stand-by mode and setpoints 
become active.  
Range is: 

0.5 to 24.0 hours

 in 0.5hr increments 

Unocc TM 

Unoccupied Timer value 
Default 

0.0 hours

 

Time delay between the moment where the thermostat toggles to stand-by mode 
and the time which the thermostat unoccupied mode and setpoints become active.
The factory value or 

0.0 hours:

 Setting this parameter to its default value of 0.0 

hours disables the unoccupied timer. This prevents the thermostat to drift from 
stand-by mode to unoccupied mode when PIR functions are used 
Range is: 

0.0 to 24.0 hours

 in 0.5hr increments 

St-By HT

  

Stand-by heating setpoint 
Default value = 

 69 °F

 

The value of this parameter should reside between the occupied and unoccupied 
heating setpoints and make sure that the difference between the stand-by and 
occupied value can be recovered in a timely fashion when movement is detected 
in the zone.  
Stand-by heating setpoint range is: 

40 to 90 °F ( 4.5 to 32.0 °C )

 

Summary of Contents for VT7300A5000

Page 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Page 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Page 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Page 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Page 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Page 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Page 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Page 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Page 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Page 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Page 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Page 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Page 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Page 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Page 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Page 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Page 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...

Reviews: