15
St-By CL
Stand-by cooling setpoint limit
Default value =
78 °F
The value of this parameter should reside between the occupied and unoccupied
cooling setpoints and make sure that the difference between the stand-by and
occupied value can be recovered in a timely fashion when movement is detected
in the zone.
Stand-by cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Unocc HT
Unoccupied heating setpoint
Default value =
62 °F
Unoccupied heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CL
Unoccupied cooling setpoint limit
Default value =
80 °F
Unoccupied cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
heat max
Maximum heating setpoint limit
Default value =
90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint adjustment.
Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit
Default value =
54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint adjustment.
Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Set Type
Temporary setpoint enable
Default is :
Permnent
Enables temporary setpoints
feature to any change of
occupied or unoccupied setpoint.
Temporar
: (temporary) Local changes to the heating or cooling setpoints by the
user are temporary. They will remain effective for the duration specified by
ToccTime. Setpoints will revert back to their default value after internal timer
ToccTime expires.
To change setpoints permanently, revert to
No
this variable or write setpoints
through the network. Any setpoints written through the network will be permanent
ones and saved to EEPROM.
Permnent
: (permanent) Any change of occupied or unoccupied setpoints through
the keypad by the user are permanent and saved to & EEPROM
TOccTime
Temporary occupancy time
Default value =
2 hours
Temporary occupancy time with occupied mode setpoints when override function
is enabled
When the thermostat is in unoccupied mode, function is enabled with either the
menu or UI2 configured as remote override input.
Range is:
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
deadband
Minimum deadband
Default value =
2.0 °F ( 1.0 °C )
Minimum deadband value between the heating and cooling setpoints. If modified,
it will be applied only when any of the setpoints are modified.
Range is:
2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5 °C increments )
cal RS
Room temperature sensor
calibration
Default value =
0.0 °F or °C
Offset that can be added/subtracted to actual displayed room temperature
Range is:
± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C increments )
cal RH
Humidity sensor calibration
Default value =
0 %RH
Offset that can be added/subtracted to actual displayed humidity by ± 15.0 %RH.
Range is :
± 15.0 %RH