4.2.3.2 Connection of the Signal Output Extension Cable
1. Route the shielded, 4-conductor signal
output cable from the LIN-300 protection box
to the receiving instrumentation through a
distinct protective conduit attached by a
liquidtight connector.
2. Remove the outer sheath of the signal output
cable on a length of 4 to 5cm
3. Strip the insulation from the individual
conductors on 7 mm (bare wire termination,
but each conductor may be fitted with a
crimped ferrule if desired).
4. Connect each pair of wires to the proper
terminals.
Figure 30 : Signal output cable connected to OUT1 and OUT2 terminal blocks
Note: A pair of terminal blocks is assigned to each LIN-300 module. To avoid mismatched configurations,
identify the conductors corresponding to each module that will be connected to the instrumentation or
acquisition/monitoring unit.
•
Top LIN-300 module =
OUT1
terminals
•
Bottom LIN-300 module =
OUT2
terminals
Table 2: Signal output cable suggested connection
Caution
To prevent damage to the LIN-300 modules, make sure power is turned off at the source before
proceeding.
OUT 1
OUT (+)
Red
GND (-)
Black
OUT 2
OUT (+)
White
GND (-)
Green