Copyright © VibroSystM Inc., 2010
35
LIN-300 Series Modules_Installation - Rev.4
O
4.2.3 Connection of modules in a protection box with optional power supply
•
An optional miniature power supply can be
installed inside the protection box.
•
When ordered with this type of power supply,
both LIN modules and power supply are pre-
wired to terminal blocks, to which two cables
must then be connected:
- the power source cable to the
Power In
AC/DC
terminals
- the signal output extension cable to the
Out1
and
Out2
terminals
•
Nominal input for miniature power supply:
AC Input voltage:100V
AC
- 240V
AC
,
(50 Hz - 60 Hz)
or
DC Input voltage:90V
DC
- 350V
DC
Figure 28 : LIN-300 Series modules inside a protection box with optional power supply
Caution
The protective conductor terminal must be connected to a grounding point in compliance
with local regulations. Grounding is essential for safety purposes as well as to provide better
efficiency against ESD and EMI perturbations.