After entering the code the appropriate menu is displayed.
It is possible to set following values:
•
Performance of ignition – it enables us to change the power of fuel ignition
•
The initial batch (s) of fuel for ignition
•
Pause in fuel feeding
•
Length of operation of feeder
•
Fan power when during the ignition
The given value can be changed when it is flashing by means of keys
and
. Transition into the next
setting after pressing the button for shift
. The output from menu after selection of icon and pressing
or
.
Other codes:
Code 1709
setting the boiler output manually– in this mode the boiler works at the output set by user
Code 1203
browsing the histogram of boiler output (for termination of browsing it is necessary to enter
again the code 1203)
Code 3105
selection of language
Code 2203
setting by manufacturer
Heating up
Setting by manufacturer
Entry into the menu takes place after long pressing
and entering relevant code. The code is entered by
means of buttons
and
and confirmed by means of button
.
For entry into this menu it is necessary to enter the code „2203“
The change of a given value is possible during its flashing by means of keys
and
. The transition to
the next setting after pressing the button of shift
. Output from the menu after selection of icon of door and
pressing
or
.
After the selection of boiler we no longer have to set manually the values of fan and feeder.
Recommended setting
Boiler
output
(kW)
Length of
feeding
(s)
The initial batch of
fuel for ignition
(s)
Pause of
feeder
(s)
Fan
power
(%)
Fan power when
during the ignition
(%)
Min.
output
(%)
25
5,4
36
5
90
10
8
16
3,5
36
7
65
10
5
We can start heating up. The correction of the boiler output can be set manually in the installation setting
(in case of failure to achieve the output because of poor quality pellets, etc.).
Temperature of
water CH
Time of heating up
Flue gas
temperature