| BL530 PH/RX DOSAGE SYSTEM
BL530 PH/RX DOSAGE SYSTEM
CONTENT BOX
The BL530 unit is supplied already wired internally, and complete with:
1. BH08014 pH electrode with 2.5 m cable and BNC connector.
2. BH08015 redox electrode with platinum sensor, 2.5 m cable and BNC connector.
3. Two PVC electrode-holders with DN50 clamp for direct in-line installation of electrodes.
4. pH and redox calibration solutions, 90 ml bottles (pH4, pH7 and 220 mV).
5. Two standard kits for peristaltic pump, including suction and
delivery tubes, foot filters and injection valves.
6. Screws and stoppers for wall installation.
7. Instruction manual.
INTRODUCTION
BL530 is a compact system easy to install (wall) and maintain, which allows to monitor and control the
pH and redox potential levels in swimming pools. The BL530 system includes a digital controller which
operates accordingly with the set thresholds, two peristaltic pumps 4 l/h, pH and redox electrodes with
BNC connector, and probe-holders.
INSTALLATION
Warning! Always follow the warnings and general safety
information referred at the beginning of this manual!
Install the BL530 unit away from heat sources, in a dry place protected from direct sunlight, at a
maximum ambient temperature of 40°C. The minimum temperature shall be such as to ensure the
solution to be dosed remains in a fluid state and in no case less than that declared in the “Technical
specifications” section. The BL530 unit must be installed on a vertical wall and securely clamped
using the supplied screws and plugs. Or when it is necessary with the fasteners suitable to the
surface. Choose a location that allows easy calibration operations, use and maintenance. Place the
tanks of the products to be dosed below the pumps, without exceeding the maximum suction
height of the pumps (about 1.5 m). If the system is installed below the level of the liquid to be
dosed, check the condition of the injection valves. Take care of tightly closed chemical containers/
tanks. Chemical fumes may cause corrosion to the dosage system, the electronics and other
materials in this place.
Connect the connectors may be disconnected for packaging reasons to the respective
inputs on the bottom of the unit (see the “Functional description” section for further details).