background image

www.fmiproducts.com

123095-01C

19

VENTING INSTALLATION

Continued

4.  Connect a section of pipe and extend 

up through hole. If an offset is needed to 

avoid obstructions, you must support vent 

pipe every 3 feet. Use wall straps for this 

purpose (see Figure 24, page 17). When-

ever possible, use 45° elbows instead of 

90° elbows. The 45° elbow offers less 

restriction to the flow of flue gases and 

intake air.

5.  Place  flashing  over  pipe  section(s)  ex

-

tending through roof. Apply a bead of 

silicone or roof sealer to the bottom flange 

of  flashing  and  secure  base  of  flashing 

to roof and framing with roofing nails. Be 

sure roofing material overlaps top edge of 

flashing as shown in Figure 24, page 17. 

There must be a 1" clearance from vent 

pipe to combustible materials.

6.  Continue to add pipe sections until the 

height of vent cap meets the minimum 

building code requirements described in 

Figure 14, page 12.

 

Note: You must increase vent height for 

steep roof pitches. Nearby trees, adjoin-

ing roof lines, steep pitched roofs, and 

other similar factors may cause poor 

draft or down-draft condition (see Figure 

24, page 17). Increasing vent height may 

solve this problem.

7.  Apply a bead of sealer to the upper edge 

of flashing collar. Slide storm collar over 

pipe  and  down  to  top  edge  of  flashing. 

Apply a second bead of silicone or roof 

sealer around remaining seam of storm 

collar. Twist-lock vent cap onto last section 

of vent pipe. Finish sealing flange around 

roofing material with roofing sealer.

Note:  If  vent  pipe  passes  through  any  oc-

cupied areas above the first floor, including 

storage spaces and closets, you must enclose 

pipe. You may frame and sheetrock enclosure 

with standard construction material. Make 

sure and meet the minimum allowable clear-

ances to combustibles. Do not fill any required 

air spaces with insulation.

Figure 27 - Cathedral Ceiling Support 

Box Installation

Cut hole 1/8"  

larger than  

support box when 

projected onto roof line

2" minimum below 

finished ceiling

Cathedral 

ceiling 

support box

Level

Cathedral Ceiling Installation

1.  Remove shingles or other roof covering as 

necessary to cut rectangular hole for sup-

port box. Mark outline of cathedral ceiling 

support box on roof sheathing using the 

locating hole as a center point.

2.  Cut hole 1/8" larger than the support box 

outline (see Figure 27).

3.  Lower support box through hole in roof 

until bottom of box extends at least 2" 

below ceiling (see Figure 27). Align sup-

port box vertically and horizontally using 

a level. Temporarily tack support box in 

place through inside walls and into roof 

sheathing.

4.  Using tin snips, cut support box from 

top corners down to roof line and fold 

resulting flaps over roof sheathing (see 

Figure 28). Apply a bead of non-hardening 

mastic around top edges of support box to 

make a seal between box and roof. Nail 

in place with roofing nails. Remove any 

combustible material that might be inside 

of support box.

5.  Complete cathedral ceiling installation 

by following the same procedures out-

lined in steps 2 through 7 for 

Flat Ceiling 

Installation, 

page 18

.

Non-hardening 

Mastic under all 

edges of support 

box before nailing

Figure 28 - Installed Cathedral Ceiling 

Support Box

f i r e - p a r t s . c o m

Summary of Contents for DVF32TMHPN-A

Page 1: ...al switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Page 2: ...only for use with the type s of gas indicated on the rating plate A conversion kit is supplied with the fireplace State of Massachusetts The installation must be made by a licensed plumber or gas fitt...

Page 3: ...vent system B Use of any component part not manu factured or approved byStyle Crest Inc in combination with a Style Crest Inc fireplace system Proper installation is the most important step in ensuri...

Page 4: ...tural and propane LP gas are odorless An odor making agent is added to the gas The odor helps you detect a gas leak However the odor added to the gas can fade Gas may be present even though no odor ex...

Page 5: ...fireplace in windy or drafty areas where curtains or other combustible flammable objects can make contact with the fireplace front in high traffic areas 4 Turn fireplace off and let cool before servi...

Page 6: ...34 3 4 3 BACK VIEW TOP VIEW Left Side Right Side Front Back 24 1115 16 101 2 11 2 11 2 101 2 FRONT VIEW 30 Opening 24 25 RIGHT SIDE 22 5 8 43 1 8 32 Opening 1 7 8 1 7 8 BACK VIEW 39 3 4 26 3 8 3 1 2 3...

Page 7: ...NTS Determine the safest and most efficient location for your Style Crest Inc direct vent fireplace Make sure that rafters and wall studs are not in the way of the venting system Choose a location whe...

Page 8: ...e 5 Minimum Clearances See Thru Shown Combustible Material Drywall 2 x 4 Stud Minimum 1 Clearance from Side Only for See Thru FRAMING Once final location has been determined observing clearances for v...

Page 9: ...quare Min Figure 12 Rough Opening for Installing Exterior Vent Terminal Vertical Height Depends on Installation 26 3 8 Horizontal Length Depends on Installation 90o Elbow 45o Elbow Figure 13 Vent Open...

Page 10: ...n line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP CLEA...

Page 11: ...against a com bustible wall Check with local codes In the USA follow the current National Fuel Gas Fuel Gas Code ANS Z223 1 also known as NFPA 54 These models are approved for use with Style Crest Inc...

Page 12: ...greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L clear...

Page 13: ...ce from fireplace flue outlet to ceiling Add ceiling thickness vertical rise in an attic or second story and allow for sufficient vent height above roof line You may use one or two 90 elbows in this v...

Page 14: ...odes Note When installing in a chase you should insulate the chase as you would the outside walls of your home This is especially im portant in cold climates Minimum clearance between vent pipes and c...

Page 15: ...bustible exterior wall 8 1 2 diameter hole if non combustible Frame as necessary Figure 17 Vent Pipe Connections Male Slots Female Locking Lugs Rigid Vent Pipe 4 Three types of vent caps are available...

Page 16: ...unit is tight and does not come loose before unit is nailed to framing Square vent or long vent configuration Vent pipe must be manipulated at outer end to make final connection Manually secure pipe...

Page 17: ...t to be used with a vertical termination 1 Determine route your vertical venting will take If ceiling joists roof rafters or other framing will obstruct venting system consider an offset see Figure 24...

Page 18: ...er the same size as ceiling joists If area above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insulation from falling into required clearance space If ar...

Page 19: ...vent pipe passes through any oc cupied areas above the first floor including storage spaces and closets you must enclose pipe You may frame and sheetrock enclosure with standard construction material...

Page 20: ...Configuration Using Two 90 Elbows VENTING INSTALLATION Continued Vertical Termination Configurations Figures 29 through 32 show four different configurations for vertical termination These minimum ve...

Page 21: ...0 feet USA you may need to decrease the input rating by changing the existing burner orifice to a smaller size Reduce input 4 for each 1 000 feet above sea level Check with your local gas company for...

Page 22: ...ed P58 12 12 Section Double Wall Pipe Galvanized P58 6 6 Section Double Wall Pipe Galvanized VENTING INSTALLATION Continued Number Description PA58 712 Adjustable 7 12 Section Double Wall Pipe Galvani...

Page 23: ...accessible distance behind louvered opening see Figure 35 You may test blower for operation by turning control knob clockwise just until it clicks on which is the full on position Adjust fan speed to...

Page 24: ...ce must be isolated from the gas supply piping system by closing its individual equipment shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less th...

Page 25: ...a leak is detected WARNING Improper installa tion adjustment alteration service or maintenance can cause injury or propertydamage Refertothismanu al For assistance or additional infor mation consult a...

Page 26: ...ght twig which is placed across top of logs B 5 Figure 44 shows the top view of burner and grate 6 Place logs A as shown in Figure 45 7 Place logs B as shown in Figure 46 page 27 Lift end of log A tha...

Page 27: ...ued PILOT ELECTRODE ASSEMBLY ADJUSTMENT The pilot assembly is factory preset for the proper flame height Alteration to these set tings may have occurred during shipping and handling If this is the cas...

Page 28: ...r s normal setting is fully open Do not forget to retighten the air shutter screw Figure 52 Burner Removal BURNER REMOVAL CAUTION Beforeproceeding toopenglassdoororhandlelogs make sure entire unit is...

Page 29: ...ts should be alerted to the hazards of high surface tem peratures andtostayawayfrom the appliance to avoid burns or clothingignition Youngchildren should be carefully supervised when they are in the s...

Page 30: ...n may result causing property damage per sonal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pi lot follow these instructions exactly B BEFORE LIG...

Page 31: ...e technician or gas supplier 9 Turn on all electric power to fireplace 10 Turn gas control knob counterclockwise to ON 11 This valve is equipped with a HI LO fea ture Set fireplace input as desired O...

Page 32: ...cian replace pilot line 7 Replace control valve see Replacement Parts and Ac cessories page 34 8 Tighten thermocouple or replace 1 Check wiring connection Refer to Wiring Diagram page 33 1 Check elect...

Page 33: ...e pilot or misaligned electrode at pilot 3 No or low gas pressure OBSERVED PROBLEM Whenignitorbuttonispressed there is no spark at pilot TROUBLESHOOTING Continued 1 Checkelectricalconnections and repl...

Page 34: ...c at 1 800 231 4822 or write to Style Crest Service P O Box 19110 Wichita KS 67204 When calling or writing please have your model and serial numbers of your heater ready RECEIVER AND HAND HELD ON OFF...

Page 35: ...la Only Black 01645 REFRACTORY PIECES Front Bottom 25854 Left Right Bottom 25856 Rear 25855 See Thru Only Rear 27374 Peninsula Only Front Bottom Left Right Bottom Rear For Peninsula and See Thru PIEZO...

Page 36: ...e write or call Style Crest Services P O Box 19110 Wichita KS 67204 800 231 4822 Collect calls not accepted 4 2 All payment for in warranty expenses shall be made to the Authorized Service Center or S...

Reviews: