Vexar CD32Ml Owner'S Operation And Installation Manual Download Page 16

www.desatech.com

111916-01F

16

Figure 34 - Converting Pilot

Pilot Hood

Pilot Orifice

Barrel Clip

5/32" Allen 
Wrench

Pilot Bracket

6.  Locate air shutter at end of burner manifold (end 

of tube burner for CD42M series). Loosen screw 

and adjust air shutter to proper setting (see 

Burner 

Flame Adjustment

, page 13). Retighten screw.

7.  Remove  pilot  hood  by  pulling  up  until  it 

disengages from barrel. Do not remove the 

retainer clip (see Figure 34).

8.  Remove pilot orifice from inside barrel using 

a 5/32" allen wrench to unscrew the orifice.

9.  Replace pilot orifice with LP orifice supplied 

with this kit. The number 30 is stamped on the 

sleeve for identification. Insert small end of 

new pilot orifice into barrel and thread until 

tight with the allen wrench.

10.  Line up notch on pilot hood to the positioning tab 

on barrel receiver and snap back into position.

IMPORTANT:

 Be careful not to bend or kink the 

aluminum tubing during conversion. Make sure 

the pilot hood and orifice are properly mated and 

aligned after finishing this conversion.

Figure 36- Installing New Parts for Gas 

Control Valve Conversion

HI

LO

O

FF  P

IL

OT

  

 O

Mounting 
Screws

Rubber 
Gasket

Identification 
Label

3.  Install the identification label enclosed with 

gas valve regulator to the valve body where 

it can easily be seen (see Figure 36).

 WARNING: The conversion kit 

must be installed by a qualified 

service technician in accordance 

with  the  manufacturers  instruc-

tions  and  all  applicable  codes 

and requirements of the authority 

having jurisdiction. If any informa-

tion is these instructions is not fol-

lowed correctly, a fire, explosion 

or production of carbon monoxide 

may result causing property dam-

age, personal injury or loss of life. 

The qualified service technician is 

responsible for the proper instal-

lation of this conversion kit.

CONVERTING FIREPLACE 

FROM NATURAL GAS TO 

PROPANE/LP GAS

Continued

CONVERTING CONTROL VALVE

Convert the gas control valve by swapping out the 

valve regulator portion of the gas valve.
1.  Using a TORX T20 or a slotted screwdriver, 

remove  and  discard  the  three  mounting 

screws,  pressure  regulator  tower  and  dia-

phragm/spring components (see Figure 35).

2.  Insure  that  the  rubber  gasket  is  properly 

positioned  on  the  new  pressure  regulator 

assembly. Install new pressure regulator as-

sembly to valve using new mounting screws 

supplied with kit. Tighten screws securely 

(approximately 25 in/lb). See Figure 36.

HI

LO

O

FF  P

IL

OT

  

 O

Figure 35- Removing Parts for Gas 

Control Valve Conversion

Diaphragm/
Spring 
Components

Mounting 
Screws

Pressure 
Regulator
Tower

Summary of Contents for CD32Ml

Page 1: ...h do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department Installa...

Page 2: ...d the Manufactured Home Construction and Safety Stan dard Title 24 CFR Part 3280 in the United States or the Mobile Home Standard CAN CSA Z240 MH Series in Canada This replace is only for use with the...

Page 3: ...uring safe and continuous operation of the replace Consult the local building codes as to the particular requirements concerned with the instal lation of all factory built replaces This replace when i...

Page 4: ...N PREPARATION CAUTION Do not block required air spaces with insula tionoranyothermaterial Donot obstruct the effective opening of the appliance with any type of facing material CLEARANCES TO COMBUSTIB...

Page 5: ...which could cause a re WARNING Horizontal sec tions of this vent system require a minimum clearance of 2 from the top of the pipe and 1 mini mum to the sides and bottom Vertical sections of this syste...

Page 6: ...ved driveway located on public property 84 inches 213 4cm minimum M clearance under veranda porch deck 12 inches 30 5cm minimum N clearance above a roof shall extend a minimum of 24 inches 61cm above...

Page 7: ...bly must be venteddirectlytotheoutside The venting system must NEVER be attached to a chimney serving a separatesolidfuelburningappli ance Each gas appliance must use a separate vent system Do not use...

Page 8: ...mination that is over 3 ft support the pipe every 3 ft using metal wall straps Vertical to horizontalpipemustbekeptata1ft to4ft ratio with a maximum run of no more than 20 ft If an offset is necessary...

Page 9: ...in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas sup ply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at...

Page 10: ...a leak Correct all leaks at once Do not operate any appliance if a leak is detected INSTALLATION Continued Figure 13 Gas Line Routing Gas Routing Right Side Not Shown Side of Fireplace Front Face Figu...

Page 11: ...place Models CD32M and CD36M A Series 1 Place log 1 back log on top of grate as shown in Figure 18 for the CD36M A Series Log 1 will go in front of the metal partition on grate see Figure 18 Make sure...

Page 12: ...log 3 rear log onto pins on rear of grate see Figure 25 4 Place log 4 crossover log onto pins from both logs 2 and 3 see Figure 26 Figure 23 Installing Log 1 Model CD42M A Figure 24 Installing Log 2 M...

Page 13: ...els must remain accessible for service Use only heat re sistant noncombustible mortar or adhesive when securing decorative facing materials FACE EXTENSION FOR MODEL CD32M ONLY Model CD32M comes equipp...

Page 14: ...necessary Turn off gas and remote switch before servicing appliance Any safety screen or guard removed for servicing the replace must be replaced prior to operation Have a quali ed agency periodically...

Page 15: ...etting 12 Turn on all electric power to the appliance Note It is recommended that you maintain the gas control knob in the full OFFposition during lengthy periods of seasonal non usage OPERATING FIREP...

Page 16: ...ll the identi cation label enclosed with gas valve regulator to the valve body where it can easily be seen see Figure 36 WARNING Theconversionkit must be installed by a quali ed servicetechnicianinacc...

Page 17: ...ement on thermocouple 3 Ensure the connection be tween valve and thermocouple are tight and secure 4 Check thermocouple with millivolt meter Take reading at thermocouple terminals of gas valve with re...

Page 18: ...1916 01F 18 6 7 19 18 10 12 23 24 34 2 11 17 8 21 2 21 6 21 4 21 5 21 3 21 1 1 13 9 16 3 14 4 20 15 5 15 42 40 35 36 22 37 39 38 25 41 26 30 27 28 29 33 31 32 ILLUSTRATED PARTS BREAKDOWN MODELS CD32M...

Page 19: ...ssover Log Log 4 1 21 5 109405 01 107348 01 Left Top Log Log 5 1 21 6 109408 01 107347 01 Right Top Log Log 6 1 22 11102 11102 Screw 8 32 x 3 8 PPH Zinc 2 23 11105 11105 Screw 10 x 1 2 Zinc 9 24 11179...

Page 20: ...com 111916 01F 20 ILLUSTRATED PARTS BREAKDOWN MODEL CD42M A 37 23 41 42 38 22 39 32 31 33 28 26 25 29 24 34 35 40 36 30 27 28 6 7 19 18 10 12 2 11 17 8 20 1 4 13 16 3 14 15 5 15 9 212 21 3 21 6 21 7 2...

Page 21: ...over Log Log 4 1 21 5 109399 01 Top Center Log Log 5 1 21 6 109400 01 Top Left Log Log 6 1 21 7 109401 01 Top Right Log Log 7 1 22 11102 Screw 8 32 x 3 8 PPH Zinc 2 23 11105 Screw 10 x 1 2 Zinc 9 24 1...

Page 22: ...P Manifold Pressure 10 w c 10 w c 10 w c Minimum Inlet Supply Pressure 4 5 w c 4 5 w c 4 5 w c WIRING DIAGRAM Thermocouple Incoming Main Gas Supply Piezo Ignitor Control Valve Electrical Rating 120v 6...

Page 23: ...2M 109479 01 CD32M SERIES BK BLOWER KIT REGULAR TRANSMITTER TRANSMITTER RECEIVER RECEIVER TRANSMITTER STANDARD REMOTE CONTROL KIT P N 14187 MILLIVOLT ONLY RECEIVER AND TRANSMITTER RECEIVER P N 00825 E...

Page 24: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com NOT A UPC 111916 01 Rev F 04 05 111916 01...

Reviews: