Cassette Type Indoor Unit’s Error Indicating:
LED
No error
Flash times
every two
seconds
Error description
yellow: Timing
indicating lamp
It goes on as per the
VHWWLPH$QGLWÀDVKHV
when the temperature
sensor error occurs
once
the indoor ambient temperature sensor error
twice
the evaporator temperature sensor error
three times
the condenser temperature senor error
four times
the outdoor ambient temperature senor error
¿YHWLPHV
the discharge air temperature sensor error
green:Compressor
indicating lamp
It goes on/off as the
compressor is turned
RQRII$QGLWÀDVKHV
when defrosting or the
compressor error occurs
twice
Defrosting
three times
high pressure protection
four times
the low pressure protection
¿YHWLPHV
Overload protection
six times
Discharge high temperature protection
red:Running
indicating lamp
It goes on/off as the
unit is turned on/off,
$QGLWÀDVKHVZKHQWKH
indoor unit error occurs
twice
WKHZDWHURYHUÀRZSURWHFWLRQ
three times
the anti-freezing error
four times
Anti-high temperature protection
2 FLOW CHART OF TROUBLESHOOTING
Service personnel shall collect the malfunction information as much as possible and research them
thoroughly, list these electrical parts which may cause malfunction, service personnel shall be able to
GHWHUPLQHWKHVSHFL¿FUHDVRQDQGVROYHWKHIDXOWHGSDUWV
z
Observe the status of the complete device and do not observe the partial
z
,WLVDGYLVHGWRVWDUWIURPWKHVLPSOHRSHUDWLRQGXULQJDQDO\]LQJMXGJLQJDQGFRQ¿UPLQJPDOIXQFWLRQUHDVRQ
WKHQFRQGXFWWKHFRPSOLFDWHGRSHUDWLRQVVXFKUHPRYDORIGHYLFHSDUWUHSODFHPHQWDQGUHIULJHUDQW¿OOLQJ
z
Find the malfunction reason carefully as unit may occur several malfunction at the same time and one
malfunction may develop into several malfunction, so entire system analysis shall be established to make
the judged result exact and credible .
Summary of Contents for CGU12N
Page 1: ...INSTRUKCJA SERWISOWA KLIMATYZATORÓW CGU FGU DGU T1 R410A 50Hz GC201109 I ...
Page 4: ...1 PRODUCT QSPEVDU ...
Page 26: ...23 CONTROL DPOUSPM ...
Page 27: ...24 QSPEVDU CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Page 28: ...25 QSPEVDU 1 2 Heating Operation ...
Page 43: ...40 INSTALLATION ...
Page 77: ...74 MAINTENANCE ...
Page 84: ...81 QSPEVDU Malfunction display E6 Communications Failure ...
Page 89: ...86 QSPEVDU 2 GU12N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 90: ...87 QSPEVDU 3 GU18N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 91: ...88 QSPEVDU 4 GU24N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 92: ...89 QSPEVDU 5 GU30N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 93: ...90 QSPEVDU 6 GU36N WITH FUNCTION OF LOW TEMP COOLING J WITHOUT FUNCTION OF LOW TEMP COOLING J ...
Page 94: ...91 QSPEVDU 7 GU36N3 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 95: ...92 QSPEVDU 8 GU42N3 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 98: ...95 QSPEVDU 3 2 3 Cassettle Type Model CGU09N CGU12N CGU18N CGU24N CGU30N CGU36N CGU42N CGU48N ...
Page 132: ...129 QSPEVDU 2 Model GU24N Exploded Views ...
Page 134: ...131 QSPEVDU 3 Model GU30N Exploded Views ...
Page 138: ...135 QSPEVDU 5 Model GU42N3 GU48N3 Exploded Views ...
Page 140: ...137 QSPEVDU 6 Model GU60N3 Exploded Views ...
Page 142: ...139 QSPEVDU 5 1 2 WITH FUNCTION OF LOW TEMP COOLING 1 Model GU09N GU12N GU18N Exploded Views ...
Page 145: ...142 QSPEVDU 2 Model GU24N Exploded Views ...
Page 147: ...144 QSPEVDU 3 Model GU30N Exploded Views ...
Page 149: ...146 QSPEVDU 4 Model GU36N GU36N3 Exploded Views ...
Page 151: ...148 QSPEVDU 5 Model GU42N3 GU48N3 GU60N3 Exploded Views ...
Page 154: ...151 QSPEVDU 5 2 Indoor Unit 5 2 1 Duct Type 1 Model DGU09N DGU12N DGU18N Exploded Views ...
Page 158: ...155 QSPEVDU 5 2 2 Cassette Type 1 Model CGU12N CGU18N Exploded Views ...
Page 160: ...157 QSPEVDU 2 Model CGU12N CGU30N CGU36N CGU42N CGU48N Exploded Views ...
Page 163: ...160 QSPEVDU 3 Model CGU30N Exploded Views ...
Page 177: ...Vidicon Ltd Commercial Air Conditioners R410A Systems ...