QSPEVDU
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
F0
Failure of Indoor Room
Sensor at Air Intake
Indoor environment
Thermal bulb
Open-circuit or short-circuit of the indoor environment thermal bulb is
detected for continuous 5 seconds, indoor environment temperature will
be set compulsively at 24 degree, the system does not take any measure,
and only the indicator is twinkling or fault code F0 is displayed. After the
fault is removed, the system can restore operation by itself. Under air
supply mode, only the fault is displayed and the indoor fan is running
normally. The fault display disappears when the fault is removed.
F1
Failure of Evaporator
Temp. Sensor
Indoor evaporator
thermal bulb
Open-circuit or short-circuit of evaporator thermal bulb is detected
IRUFRQWLQXRXVVHFRQGVXQGHUUHIULJHUDWLRQDQGGHKXPLGL¿FDWLRQ
mode, the system will be shut off; and under heating mode, all loads
except for the four way valve are shut off. The indicator is twinkling
or fault code F1 is displayed. The system can restore by itself and
display fault elimination after the fault is removed. Under air supply
mode, only the fault is displayed and the indoor unit is running
normally. The fault display disappears when the fault is removed.
F2
Failure of Condenser
Temp. Sensor
Outdoor condenser
thermal bulb
Open-circuit or short-circuit of condenser thermal bulb is detected
IRUFRQWLQXRXVVHFRQGVXQGHUUHIULJHUDWLRQDQGGHKXPLGL¿FDWLRQ
mode, the system will be shut off; and under heating mode, all loads
except for the four way valve are shut off. The indicator is twinkling
or fault code F2 is displayed. The system can restore by itself and
display fault elimination after the fault is removed. Under air supply
mode, only the fault is displayed and the indoor unit is running
normally. The fault display disappears when the fault is removed.
For other types of refrigeration machines except for air duct
machine, condenser thermal bulb is not detected.
F3
Failure of Outdoor
Ambient Sensor
Outdoor environment
thermal bulb
Open-circuit or short-circuit of outdoor environment thermal bulb
is detected for continuous 5 seconds, under refrigeration and
GHKXPLGL¿FDWLRQPRGHWKHV\VWHPZLOOEHVKXWRIIDQGXQGHUKHDWLQJ
mode, all loads except for the four way valve are shut off. The indicator
is twinkling or fault code F3 is displayed. The system can restore by
itself and display fault elimination after the fault is removed. Under air
supply mode, only the fault is displayed and the indoor unit is running
normally. The fault display disappears when the fault is removed.
F4
Failure of Exhaust
Temp. Sensor
Discharge
thermal bulb
After the compressor is started, open-circuit of discharge thermal
bulb is detected for continuous 5 seconds. Under refrigeration and
GHKXPLGL¿FDWLRQPRGHDOOORDGVZLOOEHVKXWRII8QGHUKHDWLQJPRGHDOO
loads except for the four way valve are shut off. The indicator is twinkling
or fault code F4 is displayed. And the buzzer gives out an alarm. After the
fault is removed, the system will restore by itself and clear the fault code.
If discharge thermal bulb is short circuited, under refrigeration and
GHKXPLGL¿FDWLRQPRGHDOOORDGVZLOOEHVKXWRII8QGHUKHDWLQJPRGHDOO
loads except for the four way valve are shut off. The indicator is twinkling
or fault code F4 is displayed. And the buzzer gives out an alarm. After the
fault is removed, the system will restore by itself and clear the fault code.
F5
Failure of Indoor
Room Sensor at
Wire Controller
Line controller
Open-circuit or short-circuit of line controller thermal bulb is detected
for continuous 5 seconds, indoor environment temperature will be set
compulsively at 24 degree, the system does not take any measure, and
only the indicator is twinkling or fault code F0 is displayed. After the
fault is removed, the system can restore operation by itself. Under air
supply mode, only the fault is displayed and the indoor fan is running
normally. The fault display disappears when the fault is removed.
Summary of Contents for CGU12N
Page 1: ...INSTRUKCJA SERWISOWA KLIMATYZATORÓW CGU FGU DGU T1 R410A 50Hz GC201109 I ...
Page 4: ...1 PRODUCT QSPEVDU ...
Page 26: ...23 CONTROL DPOUSPM ...
Page 27: ...24 QSPEVDU CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Page 28: ...25 QSPEVDU 1 2 Heating Operation ...
Page 43: ...40 INSTALLATION ...
Page 77: ...74 MAINTENANCE ...
Page 84: ...81 QSPEVDU Malfunction display E6 Communications Failure ...
Page 89: ...86 QSPEVDU 2 GU12N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 90: ...87 QSPEVDU 3 GU18N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 91: ...88 QSPEVDU 4 GU24N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 92: ...89 QSPEVDU 5 GU30N WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 93: ...90 QSPEVDU 6 GU36N WITH FUNCTION OF LOW TEMP COOLING J WITHOUT FUNCTION OF LOW TEMP COOLING J ...
Page 94: ...91 QSPEVDU 7 GU36N3 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 95: ...92 QSPEVDU 8 GU42N3 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING ...
Page 98: ...95 QSPEVDU 3 2 3 Cassettle Type Model CGU09N CGU12N CGU18N CGU24N CGU30N CGU36N CGU42N CGU48N ...
Page 132: ...129 QSPEVDU 2 Model GU24N Exploded Views ...
Page 134: ...131 QSPEVDU 3 Model GU30N Exploded Views ...
Page 138: ...135 QSPEVDU 5 Model GU42N3 GU48N3 Exploded Views ...
Page 140: ...137 QSPEVDU 6 Model GU60N3 Exploded Views ...
Page 142: ...139 QSPEVDU 5 1 2 WITH FUNCTION OF LOW TEMP COOLING 1 Model GU09N GU12N GU18N Exploded Views ...
Page 145: ...142 QSPEVDU 2 Model GU24N Exploded Views ...
Page 147: ...144 QSPEVDU 3 Model GU30N Exploded Views ...
Page 149: ...146 QSPEVDU 4 Model GU36N GU36N3 Exploded Views ...
Page 151: ...148 QSPEVDU 5 Model GU42N3 GU48N3 GU60N3 Exploded Views ...
Page 154: ...151 QSPEVDU 5 2 Indoor Unit 5 2 1 Duct Type 1 Model DGU09N DGU12N DGU18N Exploded Views ...
Page 158: ...155 QSPEVDU 5 2 2 Cassette Type 1 Model CGU12N CGU18N Exploded Views ...
Page 160: ...157 QSPEVDU 2 Model CGU12N CGU30N CGU36N CGU42N CGU48N Exploded Views ...
Page 163: ...160 QSPEVDU 3 Model CGU30N Exploded Views ...
Page 177: ...Vidicon Ltd Commercial Air Conditioners R410A Systems ...