Codes and Standards Information
We strongly recommend that this document is read in conjunction with the appropriate local codes and standards for smoke detection
systems and electrical connections. This document contains generic information and some sections may not comply fully with all local
codes and standards. In these cases, the local codes and standards must take precedence.
FM 3611 Hazardous Approval Warning
Exposure to some chemicals may degrade the sealing of relays used on the detector. Relays used on the detector are marked "TX2-5V" or
"G6S-2-5V" or "EC2-5NU".
UL Warning
The fire alarm threshold (signal) that initiates an evacuation procedure via the Fire Alarm Panel must not be set higher than 0.625%/ft. The
detector can send this signal either via the Fire Alarm Panel Output signal or the Pre-alarm output signal.
Safety Label
This VESDA product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA regulations 21 CFR
1040.10. The laser is housed in a sealed detector chamber and contains no serviceable parts. This laser emits invisible light and can be
hazardous if viewed with the naked eye. Under no circumstances should the detector chamber be opened.
Document: 10279_01
This product complies with the following standards
SSL AS1603.8-1996
LPC & VdS GEI 1-048:Jan 1997
UL & CUL UL268 UL268A
FM FM3230-3250 FM3820
FDA 21 CFR 1010.2 21 CFR 1010.3
VESDA AS2211 EN60950
AS/NZS 3548 FCC Class B
EN 50081-1 EN 50130-4
UL and FM Compliancy
All installers must ensure that environments that require UL approved product must have the requirements of a remote display or FACP
connected to the detectors. Failure to do so will void product compliance for UL and FM certification that is stated on the detector approval
and rating label.
Approval Certification:
Vision Fire & Security have had this product tested and approved by UL and FM. This product is fully listed and compliant as long as the
exception in UL268 is adhered to. Please see section 17.5 of UL268, 2003 Edition.
“17.5 A lamp or equivalent means shall be provided on a spot-type detector head or base to identify it as the unit from which the alarm was
initiated”.
Exception:
The alarm-indicating-means is not required on a detector whose use is restricted to a specific control unit that identifies
the individual detector in alarm.
As long as these models are connected to a remote display or to a Fire Alarm Control Panel (FACP) that identifies if the detector is in alarm
then it is a compliant product.
Australia and Asia
The Americas
Europe & Middle East
Vision Systems
Private Bag 215
495 Blackburn Road
Mount Waverley VIC 3149
Australia
Toll free: 1800 700 203
Tel: +61 (0) 3 9211 7200
Fax: +61 (0) 3 9211 7201
Vision Systems
700 Longwater Drive
Norwell,
Massachusetts, 02061
USA
Toll free: 800 229 4434
Tel: +1 78 740 2223
Fax: +1 78 740 4433
Vision Systems
Vision House, Focus 31,
Mark Road
Hemel Hempstead
Hertforshire HP2 7BW
United Kingdom
Tel: +44 (0) 1442 242 330
Fax: +44 (0) 1442 249 327