LaserSCANNER Product Manual
VESDA
®
18
Relay default settings
Table 3 - Table showing the default settings for relays
Note:
A
D
represent the Default Relay Settings. Relays 3 and 6 are permanently
configured for Urgent Fault and Fire 1 (any sector) respectively. All other relays can
be re-configured. Multiple functions can be attached to a relay provided the
combined voltage does not exceed 5 VDC.
Relay
1
2
3
4
5
6
7
8
9
10
11
12
Isolate
D
Minor Fault
D
Urgent Fault
D
Alert Sector 1
D
Alert Sector 2
D
Alert Sector 3
D
Alert Sector 4
D
Action Sector 1
D
Action Sector 2
D
Action Sector 3
D
Action Sector 4
D
Fire 1 Sector 1
D
Fire 1 Sector 2
D
Fire 1 Sector 3
D
Fire 1 Sector 4
D
Fire 2 Sector 1
D
Fire 2 Sector 2
D
Fire 2 Sector 3
D
Fire 2 Sector 4
D
first alarm sector 1
D
first alarm sector 2
D
first alarm sector 3
D
first alarm sector 4
D
Scanning
D