VESDA
®
LaserSCANNER Product Manual
11
1.4
LaserSCANNER
Product Information
Product Specifications
Supply Voltage
18 to 30 VDC
Power Consumption
@24 VDC
LaserSCANNER with Blank
Plates 3,000rpm
Normal: 5.8 W
Alarm On: 7.4 W
LaserSCANNER with Blank
Plates @ 4,200rpm
Normal: 9.6 W
Alarm On: 12 W
Programmer Module
Normal: 0.6 W (Backlight Off)
Alarm On: 2.2 W (Backlight On)
Display Module
Normal: 1.6 W
Alarm On: 2.2 W
Dimensions (WHD)
350 mm x 225 mm x 125 mm (13.8 in x 8.9 in x 4.9 in)
Weight
4.0 kg (9 lbs) including Display and Programmer
Modules
Operating Temperature
(To operate the
LaserSCANNER detector
outside these parameters
please contact your nearest
VESDA Technical Office)
Detector Ambient:
UL tested: 0° to 39° C (32° F to 103° F)
Sampled Air: -20° to 60° C (-4° to 140° F)
Humidity: 10-95% RH, non-condensing
Storage Temperatures
(Non-operational)
Up to 2 years (battery life). 0° to 85°C
Dry (<95% humidity)
0° to 85° C
Must not be exposed to sunlight or other radiation
sources
Sampling Pipe Network
Maximum length per pipe 100 m (328 ft)
Aggregate pipe length: 200 m (650 ft)
Pipe Modelling Design Tool: ASPIRE™
Pipe Size
Internal Diameter: 15-21 mm (9/16 - 7/8 in)
External Diameter: 25 mm (1 in)
(25 mm to 1 inch adaptor supplied for USA market)
Relays
7 or 12 relays option. Contacts rated 2A @ 30 VDC
Programmable to latch or non-latch states.