VESDA VLQ Product Guide
VESDA by Xtralis
24
www.xtralis.com
4.2.7
Wiring to an Addressable Loop Module
This wiring example is for wiring VESDA detectors to a typical Input/Output Loop module 3 inputs 1 output.
Note:
These are example drawings. Refer to the appropriate product manual for the exact wiring details of
the third party equipment.
Normally Closed (NC)
Common (C)
FIRE
(NO)
Normally Open
Normally Closed (NC)
Common (C)
FAULT
(NO)
Normally Open
GPI
)
(Set to reset
Dete tor
c
(NC)
(C)
Reset
(NO)
Fire Input
Short = Fire
Open = Wiring Fault
3
1
Inputs
Output Loop Module
To FACP
To Next Detector
Fault Input
Short = Detector Fault
Open = Wiring Fault
EOL*
EOL*
*EOL: End of Line Resistor
EOL*
Figure 4-15: Input/Output Loop Module with EOL