21
4.1.3.2
Mounting without Junction Box
A
B
C
Legend
A
Ceiling or Ceiling Tile
B
Flush Mount Bracket
C
Detector Base Holes
Figure 4-11: Flush Mount on suspended Ceiling Tile with no Junction Box
1. Follow steps 1 to 5 from the previous section.
2. Pass the wires through the detector base holes (C).
3. Feed wires through the wire retaining strip on the base of the detector and attach to the appropriate
terminal block connectors.
4. Fit the terminal bock connectors to the appropriate sockets on the terminal block.
5. Align detector base body to the detector body so that there is room to rotate it anti-clockwise, ensuring
that pipe inlets match the arrows shown on the detector body.
6. Support the flush mount bracket in the ceiling void in accordance with local electrical codes.
7. Insert pipes into the pipe inlets and seat them tightly. Use short capillary tubes (maximum 30cm/1ft) with
appropriate sampling heads.