VESDA-E VEP-A00-P Product Guide
70
www.xtralis.com
5.5.10 Relay Options
The Relay options page provides the ability to determine which alarm or fault condition is assigned to each
relay and whether each condition is latched. In addition, each relay can be configured Normally Energized or
Normally De-Energized.
Figure 5-21: Relay Options
Relay Assignments:
Select the conditions you want to assign to each relay by checking the checkbox(es)
under the relay. The following checkboxes cannot be changed:
l
Relay 6 always reports Fire 1
l
Relay 3 always reports Urgent Fault and is always Normally Energised.
You can assign more than one condition to a relay.
Normally Energized:
The Normally Energized or Normally De-Energized setting of each relay can be
configured using the checkbox in the Normally Energized row:
l
If checked the relay is set Normally Energized.
l
If unchecked the relay is set Normally De-energized.
In the Normally De-energized mode no drive is applied to the relay coil until the assigned condition such as
Alert or Fire 1 occurs. The Normally Energized mode is the opposite. Drive is removed from the relay coil
when the condition occurs.
The default mode of the relays is listed in Table 4-2.
Latching:
If the cause of a condition is removed (for example, smoke decreases below the threshold) and
latching is enabled, the detector “remembers” the condition and holds the corresponding relays and displays in
the active state as though the cause of the condition were still active.
Latching can be enabled for any alarm condition or for urgent or minor fault by checking the corresponding
latching checkbox to the right of the condition.
Beep:
The detector's buzzer can be configured using the checkboxes under heading "Beep". If checked the
buzzer will beep when the condition occurs.
Summary of Contents for VESDA-E VEP-A00
Page 2: ......
Page 10: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEP A00 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEP A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A00 P Product Guide 106 www xtralis com Z zone 57 59 77 101 ...