VESDA-E VEP-A00-P Product Guide
6
www.xtralis.com
2.3
Front Panel
The VEP-A00 detector provides the following information and control capability:
l
Status LEDs:
Alert, Action, Fire 1, Fire 2, Disabled, Fault and Power.
l
Controls:
Reset and Disable button.
2.3.1
Status LEDS
The VESDA-E VEP-A00 detector features a range of LED Indicators which illuminate when their respective
activation conditions are met.
LED
Symbol
Description
Fire 2
The Fire 2 LED is lit when the Fire 2 Alarm threshold is
reached. (The LED will flash once per second until the
condition is acknowledged.)
Fire 1
The Fire 1 LED is lit when the Fire 1 Alarm threshold is
reached. (The LED will flash once per second until the
condition is acknowledged.)
Action
The Action LED is lit when the Action threshold is reached.
(The LED will flash once per second until the condition is
acknowledged.)
Alert
The Alert LED is lit when the Alert threshold is reached. (The
LED will flash once per second until the condition is
acknowledged.)
Disabled
The DISABLED LED is lit continuously when the detector is
disabled and flashes once every two seconds when the
detector is in Standby mode.
Fault
The FAULT LED is lit when a fault condition is detected. The
LED will flash once per second until the condition is
acknowledged.
Refer to Chapter 8 for information on troubleshooting.
Power
The POWER LED illuminates when the detector is powered
up.
Table 2-1: LED Indicators
Notes:
l
The LEDs are tested during the power up cycle. To manually test the LEDs, run the Lamp Test using
Xtralis VSC.
2.3.2
RESET / DISABLE / ACKNOWLEDGE Button
Figure 2-2: Reset / Disable / Acknowledge Button
If there is an alarm or fault condition pressing the button the first time will acknowledge the condition.
Subsequent presses will reset or disable the detector.
Resetting the detector unlatches all latched alarms and faults, returns relays to their normal state and clears
the active event list in Xtralis VSC.
l
To reset the detector once all alarms and faults have been acknowledged, press this button once.
Disabling the detector disables signaling of alarms and faults via the relays. The aspirator remains active.
Summary of Contents for VESDA-E VEP-A00
Page 2: ......
Page 10: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEP A00 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEP A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A00 P Product Guide 106 www xtralis com Z zone 57 59 77 101 ...