VESDA-E VEP-A00-P Product Guide
16
www.xtralis.com
screwdriver in the large slot and twist, or use a small screwdriver in the side slots to lever the plug out.
l
Insert the pipes into the pipe inlet(s) ensuring a firm fit.
Note:
DO NOT glue the inlet pipes to the pipe inlet manifold.
When configuring the detector ensure that the correct pipes in use are selected as indicated in Table 3-1.
No. of Pipes
Preferred Pipe Inlet Port to use
Pipe 1
Pipe 2
Pipe 3
Pipe 4
VEP-A00-P
1
Inlet 2 or 3
Inlet 2 or 3
2
3
Inlet 1 or 4
Inlet 1 or 4
4
VEP-A00-1P
1
Table 3-1: Preferred use of pipe inlet ports
1
2
3
4
Figure 3-1: Pipe inlet port numbering
For code-specific information, refer to Codes and Standards Information for Air Sampling Smoke Detection on
page iii.
3.4
Managing the Exhaust Air
Air is expelled from the detector via the exhaust port at the bottom of the unit enclosure.
The air exhaust port is tapered to accommodate standard pipes of OD 25 mm (ID 21 mm) and to provide an
airtight seal. IPS ¾ inch pipes (1.05 inch OD) require an adaptor (VSP-961) as shown in Figure 3-2. If required,
connect an outlet pipe to the exhaust manifold. DO NOT glue this pipe to the exhaust manifold as this will void
the warranty.
Figure 3-2: Imperial Pipe Adaptor (VSP-961)
Where the detector is located outside the protected environment, it may be necessary to return the exhaust air
to the same environment. For example, where pressure differences exceed 50 Pa, or where hazardous
substances are present inside the protected environment. Return air pipes need to be as short as possible to
minimize the effect of airflow impedance in the return air pipe network.
Summary of Contents for VESDA-E VEP-A00
Page 2: ......
Page 10: ...VESDA E VEP A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEP A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEP A00 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEP A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A00 P Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A00 P Product Guide 106 www xtralis com Z zone 57 59 77 101 ...