Required EOL for each set of Terminals: 6.8k Ohm Resistor (S2027) and 470 Ohm Trigger Resistor (S2051)
The Abort input is not used on systems intended to perform pre-action or deluge water functions. These
systems disallow the use of an Abort switch.
Systems which incorporate the use of a manual release and release Halon 1301, water mist, aerosol, and/or
clean agents must additionally employ a mechanical manual release.
CIE Serial
These terminals are used to connect the XT+ unit to the Elite RS panel. Refer to
for wiring information for the CIE Serial terminals.
Status Serial / Status Pow.
These terminals are used when connecting a Status Unit to the XT+. Refer to the
for model
numbers of that unit.
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 30
Installation