The XXX displayed here is the EXISTING value to which the monitoring level is set and corresponds to the
Exting. 1 (Main)
output on the module.
To recalibrate
Exting. O/P 1
, press
Enter
. The LCD will display:
The
XXX
shown here is the NEW value detected for the extinguishing output. Press
Enter
to store that level.
The monitoring level is then learned by the unit and any active trouble will restore. A new trouble will occur if the
electrical characteristics on this output change.
Press
(+)
to display and set the monitoring level for output 2 in the same way as output 1.
IMPORTANT!
After calibration of these outputs, testing should be done to confirm proper operation of the
extinguishing system.
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES