Removing Cabinet Components
Remove the door, fascia, and power supply before mounting the cabinet box. To remove these components:
1. Disconnect all wires and cables between the door/fascia and the cabinet.
2. Remove the hinge pins of the fascia and then remove it from the cabinet box. Return the hinge pins to the
hinges of the cabinet box for safekeeping.
3. Remove the hinge pins of the door. Return the two hinge pins to the hinges of the cabinet box for safe-
keeping.
4. Disconnect the power supply and remove it from the cabinet.
5. Mark hole locations on the wall for mounting the empty cabinet.
6. Drill holes and anchor the empty cabinet box to the wall using appropriate mounting hardware to secure
it.
7. Remove the necessary number of knockout tabs from the cabinet box and feed external cabling into the
unit.
WARNING!
Separate high and low voltage wiring in the enclosure with a minimum gap of 0.25". Do not route low
voltage cabling through the same conduit as AC lines. AC power lines should be threaded through a dedicated
conduit.
Replacing Cabinet Components
1. Replace the power supply.
2. Replace the door and fascia.
3. Reconnect the cabling.
4. Install the standby batteries.
Installing the Power Supply
The XT+ is equipped with a 5.25 Amp power supply. Set DIP switches on the power supply before completing
the installation process. Refer to
. The power supply settings must be performed to
establish the optimal charge current of the standby batteries. These power supplies can be set to operate at
Installation
VES Fire Detection Systems
XT+ Releasing Control Unit Installation Manual
Version 1.00 | December 2018 | MAN-1252VES
Page 19