VERTIV INTELLIGENT RACK PDU
Page 90
Figure 3-56 SNMP Traps/Types IP Configuration Page
To configure a trap destination:
1. Locate the
Traps
section of the SNMP page, and click on the Add icon.
2. Enter the IP Address which the trap should be sent to in the
Host
field, change the
Port
number if
required, select the trap
Version
to be used (v1, v2c, or v3), and click
Save
.
A test trap may be sent by clicking on the Test icon next to the Host IP address. Trap settings can also be
updated/changed by clicking the Modify icon next to the Host IP address.
5.5.11.
SYSLOG
Syslog data can be captured remotely but must first be setup and enabled via the Syslog page.
NOTE
This function is primarily only useful for diagnostic purposes, and should
normally be left Disabled unless advised to enable it by Vertiv technical sup-
port for troubleshooting a specific issue.