52 Appendix 1 Technical Parameter
NetSure 801 AG1 Power Supply System User Manual
Appendix 1 Technical Parameter
Table 1 Technical parameters
Parameter
Category
Parameter
Description
Environmental
Operating temperature range
-10°C to 55°C (derating from 40°C)
Storage temperature range
-25 ~ 55
℃
Transport temperature range
-40 ~ 70
℃
Relative humidity
5%RH ~ 95%RH
Altitude
≤ 2000m (derating is necessary above 2000m)
Over-voltage level
Level II
Pollution level
Level II, No conductive dust and corrosive gas. No dangerous of explosive
AC input
AC input system
3-phase 4-wire or 3-phase 5-wire
Rated input line voltage
380Vac
Input voltage range
260Vac ~ 530Vac
Input AC voltage frequency
45Hz ~ 65Hz
Max input current
≤ 12A × n (n representing the amount of the rectifier), at 304Vac input
DC output
Rated voltage
-53.4Vdc
Output DC voltage
-42Vdc ~ -57.6Vdc
Max output current
≤ 121A × n (n representing the amount of the rectifier)
Total regulation
≤ 1%
Efficiency
≥ 90%
Noise voltage (peak-peak
≤ 200mV (0 ~ 20MHz)
Telephone psophometrically
weighted noise voltage
≤ 2mV (300Hz ~ 3400Hz)
Wide frequency noise voltage
≤ 100mV (3.4kHz ~ 150kHz); ≤ 30mV (150kHz ~ 30MHz)
Discrete noise
≤ 5mV (3.4kHz ~ 150kHz); ≤ 3mV (150kHz ~ 200kHz); ≤ 2mV (200kHz ~
500kHz);
≤ 1mV (0.5MHz ~ 30MHz)
AC input alarm
and protection
AC input overvoltage alram point
Default: 25%, configurable through controller
AC input undervoltage alarm point Default:25%, configurable through controller
AC input overvoltage/undervoltage
alarm hysteresis
Fixed:
≤ 5%
AC input overvoltage protection
point
Default: 535 ± 5Vac (line voltage), configurable through controller, hysteresis is
more than 10Vac
AC input undervoltage protection
point
Default: 255 ± 5Vac (line voltage), configurable through controller, hysteresis is
more than 15Vac
DC output
alarm and
protection
DC output overvoltage 2 alarm
point
Default: -58.5 ± 0.3Vdc
DC output overvoltage 1 alarm
point
Default: -55.7 ± 0.3Vdc
DC output undervoltage 1 alarm
point
Default: -45.0 ± 0.3Vdc
DC output undervoltage 2 alarm
point
Default: -42.0 ± 0.3Vdc
DC input overvoltage/undervoltage
alarm hysteresis
Fixed : 0.5Vdc
Rectifier
Current sharing
Rectifiers can work in parallel and share the current. The unblanceness is
better than ±3% rated current. Test current range: 10% ~ 100% rated current
Derate by input (45°C)
The rectifier can output max. power of 5,800W with input voltage of 304Vac ~
530Vac.
The output power will drop to 50% rated power when the input volatage fall to
304Vac ~ 260Vac