Chapter 3 Installation 23
NetSure 801 AG1 Power Supply System User Manual
Rectifier
cabinet
Rectifier
cabinet
Rectifier
cabinet
DC
cabinet
DC
cabinet
DC
cabinet
3.2.5 Placing DC Cabinet Separate From System
The NetSure801 power supply system uses integrated monitoring, the DC distribution cabinet can be placed separate
from the system, and typically where loads are grouped, for example, on different floors. When connecting the DC
distribution cabinet to the system, use cable to connect between the parallel connection bars. Pay attention to the
following points:
Use cable rather than copper bar to connect between the parallel connection copper bars of the DC distribution
cabinet and the system to ensure accurate measurement of load current. The connecting points are the
installation holes for parallel connection copper bar.
Communication inside the system uses CAN mode.
3.3 Connecting Power Cables
Note
Before electrical connection, turn off all of the switches and fuses.
The accessory cables used in cable connection are given in Table 3-1.
Table 3-1 Accessory cables used in cable connection
BOM
Description
Length
04111819
W24GASL05 cable suite (CAN communication cable)
4.2m
04115520
W74C5FSL1 cable suite (temperature sensor cable)
10m
3.3.1 Connecting Earth Cable
The power supply system uses common earth. The connection procedures are as follows.
1. Use the earth cable to connect the earth terminal of the rectifier cabinet to the earth terminal of the DC distribution
cabinet (see Figure 3-8).