Vertiv | Liebert XDH | User Manual
8
Pre-Installation
2.3.Storage & Operating Environmental Requirements
2.3.1.Operating Environment
The operation environment of XDH precision air conditioner meets the requirements of GB4798.3-2007. See
for details.
Table 2-2 Operating Environment Requirements
Items
Requirements
Ambient temperature
Indoor temperature: 18 °C to 40 °C, RH<60%
Protection level (cooling unit)
IP20
Altitude
<1000 m, Derating is required when located altitude is above 1000 m
Operation voltage range
220 V
±
10%, 1 Ph, 50 Hz/ 60 Hz
Contamination level
Level II
2.3.2.Storage Environment
The storage environment of XDH precision air conditioner meets the requirements of GB4798.1-2005. See
for details.
Table 2-3 Storage Environment Requirements
Items
Requirements
Storage Environment
Clean room (no dust)
Environment humidity
Less than 95% RH
Ambient temperature
-25 °C to +55 °C
Storage time
Total transportation and storage time should not exceed six months,
otherwise the performance of the system needs to be re-calibrated.
Please contact Vertiv local representative when operating in the following conditions
•
The voltage of the air conditioning unit is beyond the range of the operating voltage.
• The altitude is higher than 1000 m.
•
If the application condition is other than