Vertiv | Liebert PEX+ Chilled Water | User Manual
44
Electrical Installation
The cable sizes should meet the local wiring regulations.
Table 3-1 Rated Full Load Ampere (FLA) (unit: A)
Model
Full Load Amps
(Fans only – no
heating and no
humidification
Unit with 1 Stage
Heating
(No humidifica-
tion)
Unit with 2 Stage
Heating
(No humidifica-
tion)
Unit with
Electrode
Humidifier
(No heating)
Unit with
Infrared
Humidifier
(No heating)
(A)
(B)
(C)
(D)
(E)
P1030
5.4
15.4
25.4
10.8
11.5
P1040
5.4
15.4
25.4
10.8
11.5
P1050
5.4
15.4
25.4
10.8
11.5
P1060
5.5
15.5
25.5
10.9
11.6
P2070
10.8
25.9
40.9
21.6
23.0
P2080
10.8
25.9
40.9
21.6
23.0
P2090
10.8
25.9
40.9
21.6
23.0
P2100
10.8
25.9
40.9
21.6
23.0
P2110
11.0
26.1
41.1
21.8
23.2
P2120
11.0
26.1
41.1
21.8
23.2
P2130
11.0
26.1
41.1
21.8
23.2
P2140
11.0
26.1
41.1
21.8
23.2
P3150
16.2
36.2
56.2
27.0
28.4
P3160
16.2
36.2
56.2
27.0
28.4
P3170
16.5
36.5
56.5
27.3
28.7
P3180
16.5
36.5
56.5
27.3
28.7
P3190
16.5
36.5
56.5
27.3
28.7
P3200
16.5
36.5
56.5
27.3
28.7
•
The standard model is configured with humidifier and 1-stage electrical heater.
•
The FLA of the standard unit is the same as the unit fitted with 1-stage heater (no humidifier).
•
MCB and cable sizes are selected as per the local electrical standards.