Vertiv | Liebert PEX+Chilled Water | User Manual
58
iCOM Controller Operation
Parameters
Default
Setting Range
Description
U232
HIREM 09
32.3 °C
1.0 - 99.0 °C
High Remote Temperature 09
U232
LOREM 09
12.8 °C
1.0 - 99.0 °C
Low Remote Temperature 09
U233
HIREM 10
32.3 °C
1.0 - 99.0 °C
High Remote Temperature 10
U233
LOREM 10
12.8 °C
1.0 - 99.0 °C
Low Remote Temperature 10
U235
STPR MSG
0 (Disabled) 0 = No
1 = Yes
Static Pressure Message Enable
U236
HI STAT
320 Pa
2 - 350 Pa
High Static Pressure Alarm Border Pa
U237
LO STAT
0 Pa
0 - 348 Pa
Low Static Pressure Alarm Border Pa
U238
STAT OFF
0 (No)
0 = No
1 = Yes
Stat Pres Msg Disable for Unit Off
U239
STAT FAN
0 (No)
0 = No
1 = Yes
Stat Pres Msg Disable for Fan Events
U240
HI RANG
320 Pa
0 - 350 Pa
SP Transducer High Range Pa
U241
LO RANG
0 Pa
0 - 348 Pa
SP Transducer Low Range Pa
To browse through the menu, press the enter button to highlight the option, and use the up or down button to
scroll. Password is required for changing the setpoints. Then, enter the SET ALARMS menu, press the enter
button to highlight the option, use the up or down button to browse the submenu. Press the enter button to enter
the selected parameter. Use the up or down button to change the setpoints, and press the enter button to save
the change, or press the ESC button to quit the change.
4.5.6. Sensor Data
The data acquired can be monitored by the sensors through the SENSOR DATA menu. The values are read only;
no setting or change is allowed.
4.5.7. Display Setup
The DISPLAY SETUP menu is used to set the LCD display attributes. Password is not required for changing the
setpoints. The parameters are described in the