Vertiv | Liebert PEX+Chilled Water | User Manual
61
iCOM Controller Operation
4.5.9. Sleep Mode
In the sleep mode, the air conditioner unit can realize auto-On/ Off. Through the SLEEP MODE menu, you can set
two-time zones of the sleep mode, and select the sleep timing mode. The parameters on this menu are described
in
Table 4-9 Descriptions of SLEEP MODE Parameters
Parameters
Default
Setting Range
Description
U602
SLEEP EN
0 (No)
0 = No
1 = Yes
Sleep Mode Enable
U604
MON
0 (No)
0 = No
1 = Yes
Sleep on Monday
U604
TUE
0 (No)
0 = No
1 = Yes
Sleep on Tuesday
U604
WED
0 (No)
0 = No
1 = Yes
Sleep on Wednesday
U604
THU
0 (No)
0 = No
1 = Yes
Sleep on Thursday
U604
FRI
0 (No)
0 = No
1 = Yes
Sleep on Friday
U604
SAT
0 (No)
0 = No
1 = Yes
Sleep on Saturday
U604
SUN
0 (No)
0 = No
1 = Yes
Sleep on Sunday
U606
START 1
0
Time (hh)
Sleep 1 from (hour)
0
Time (mm)
Sleep 1 from (minute)
STOP 1
0
Time (hh)
Sleep 1 to (hour)
0
Time (mm)
Sleep 1 to (minute)
U608
START 2
0
Time (hh)
Sleep 2 from (hour)
0
Time (mm)
Sleep 2 from (minute)
STOP 2
0
Time (hh)
Sleep 2 to (hour)
0
Time (mm)
Sleep 2 to (minute)
U609
TIME MOD
0 (No)
0 = No
1 = Yes
2 = Auto
Timer Mode
U610
TIME TYP
0 (Sys
Off)
0 = S.OFF
1 = DEADB
Timer Mode Type
U611
DEADBAND 2.3 K
2 to 15 K
Deadband for Timer Mode
4.6. Service Info
The SERVICE INFO menu provides the contact information of customer service personnel. This information is read
only.