background image

33 

 

 

6. Specifications 

MODEL 

GXT-MT+ 10KVA LX (3x3) L 

CAPACITY 

10000VA / 9000W 

INPUT 

Voltage 
Range 

Low Line Loss 

110 VAC(Ph-N) ± 3 % at 50% Load 

176 VAC(Ph-N) ± 3 % at 100% Load 

Low Line Comeback 

Low Line Loss V 10V 

High Line Loss 

300 VAC(L-N) ± 3 % at 50% Load 

276 VAC(L-N) ± 3 % at 100% Load 

High Line Comeback 

High Line Loss Voltage - 10V   

Frequency Range 

46Hz ~ 54 Hz @ 50Hz system 
56Hz ~ 64 Hz @ 60Hz system 

Phase 

Three phase with Neutral 

Power Factor 

  0.99 at 100% Load 

OUTPUT 

Phase 

Three Phase with Neutral 

Output voltage 

3 x 400 VAC (3Ph+N) 

AC Voltage Regulation   

± 1% 

Frequency Range   
(Synchronized Range) 

46Hz ~ 54 Hz @ 50Hz system 
56Hz ~ 64 Hz @ 60Hz system 

Frequency Range (Batt. Mode) 

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz 

Overload 

AC mode 

100%~110%: 10min 

110%~130%: 1min 

>130% : 1sec 

Battery mode 

100%~110%: 30sec 
110%~130%: 10sec 

>130% : 1sec 

Current Crest Ratio 

3:1 max 

Harmonic Distortion 

  2 % @ 100% Linear Load; 

  5 % @ 100% Non-linear Load 

Transfer 
Time 

Line

Battery 

0 ms 

Inverter

Bypass 

0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) 

Inverter

ECO 

<10 ms 

EFFICIENCY 

AC mode 

> 89% 

Battery Mode 

> 86% 

BATTERY 

Type 

Depending on applications 

Numbers 

18 - 20 

Recharge Time 

Depending on external battery capacity 

Charging Current   

12.0 A ± 10% (max.)

 

Charging Voltage   

273 VDC ± 1%   

PHYSICAL 

Dimension, D X W X H (mm) 

592X250X826 

Net Weight (kgs) 

38 

ENVIRONMENT

 

Operation Temperature 

0 ~ 40°C (the battery life will down when > 25°C) 

Operation Humidity 

<95 % and non-condensing 

Operation Altitude* 

<1000m 

Acoustic Noise Level 

Less than 60dB @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008, Windows®  7, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

*If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. 
**Product specifications are subject to change without further notice.   

Summary of Contents for Liebert GXT-MT+10KVA

Page 1: ......

Page 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Page 3: ...2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 7 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 SINGLE UPS OPERATION 11 3 5 PAR...

Page 4: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Page 5: ...ipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presence...

Page 6: ...mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Condu...

Page 7: ...s The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One share current cable on...

Page 8: ...for parallel model 5 Parallel port only available for parallel model 6 Intelligent slot 7 Power stage fan 8 External battery connector 9 Bypass Input Circuit Breaker Only available for dual input uni...

Page 9: ...x3 LB 10 10 8 8 8 NOTE 1 The cable should be able to withstand over 40A current It is recommended to use AWG 10 or thicker wire for Phase and AWG 8 or thicker wire for Neutral for safety and efficienc...

Page 10: ...ake sure the voltage of the battery pack is correct Pay highly attention to the polarity marking on external battery terminal block and make sure the correct battery polarity is connected Wrong connec...

Page 11: ...8 Wiring diagram of parallel system 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown...

Page 12: ...play next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press this button to...

Page 13: ...put and output voltage frequency battery voltage load information and internal temperature Vac input output voltage Vdc battery voltage Hz frequency load level C F temperature Load information Indicat...

Page 14: ...rotect your precious devices you should turn on the UPS Refer to next step 2 Press and hold the ON button for 0 5s to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will e...

Page 15: ...n bypass acceptable range it will cut off output directly 4 Charge the batteries 1 After the UPS is connected to the utility power the charger will charge the batteries automatically except in Battery...

Page 16: ...section 6 Test the batteries 1 If you need to check the battery status when the UPS is running in AC mode CVCF mode you could press the Test button to let the UPS do battery self test 2 Users also can...

Page 17: ...urn off the UPS If the load couldn t be cut off you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the line i...

Page 18: ...tion 3 4 7 Then follow the wiring procedure in section 2 4 4 Remove the cover of parallel share current cable port on the UPS connect each UPS one by one with the parallel cable and share current cabl...

Page 19: ...If the bypass is abnormal you can not remove the UPS without interruption You must cut off the load and shut down the system first 2 Make sure the bypass setting is enabled in each UPS and then turn o...

Page 20: ...BD Not allowed OPN Allow CHE Check RES Reserved L1 The first line L2 The second line L3 The third line 3 7 LCD Setting 3 7 1 LCD Main Interface A Single model Press up and down key to select the displ...

Page 21: ...unit 3 7 2 LCD Setting At the main interface press and hold the up and down buttons simultaneous for more than 1 second to enter or escape from setting menu Parameter 1 Parameter 2 There are two param...

Page 22: ...ptions 18 Reserved 19 Reserved 20 Neutral loss detection Y Y Y Y Y Y 21 Battery voltage calibration Y Y Y Y Y Y 22 Charger voltage adjustment Y Y Y Y Y Y 23 L1 inverter voltage adjustment Y Y Y 24 L2...

Page 23: ...uency is not within 46 54 Hz If 60 Hz is selected in Output frequency setting UPS will transfer to battery mode when input frequency is not within 56 64 Hz Note For single unit it will have bypass out...

Page 24: ...ss mode Interface Setting Parameter 2 Set the acceptable high frequency for bypass 50 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0H...

Page 25: ...ble disable Interface Setting Parameter 2 Enable or disable phase auto adapt function You may choose following two options DIS disable phase auto adapt function Then the UPS only can accept one condit...

Page 26: ...or example pressing OFF button in AC mode to turn into Bypass mode 16 Maximum battery discharge time setting Interface Setting Parameter 2 001 999 Set the maximum backup time from 1 min to 999 min UPS...

Page 27: ...enerated If the UPS is turned on it will transfer to battery mode When neutral is restored the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode automatically Here you...

Page 28: ...ng the default value 0 Any modification should be suitable to battery specifications 23 L1 inverter voltage adjustment Interface Setting Parameter 2 The voltage range is from 9 9V to 9 9V the default...

Page 29: ...meter The calibration result will be effective by pressing Enter The calibration range is limited within 9V This function is normally used for parallel operation 28 L3 output voltage calibration Inter...

Page 30: ...able AC power to output The UPS will also charge the battery at AC mode ECO mode When the input voltage frequency is within acceptable range and ECO mode is enabled UPS will bypass voltage to output f...

Page 31: ...t start failure None 29 Battery fuse broken in Battery mode None 12 High inverter voltage None 36 Parallel output current unbalance None 13 Low inverter voltage None 41 Over temperature None 14 Invert...

Page 32: ...ode Warning event 01 Battery unconnected 10 L1 IP fuse broken 02 IP Neutral loss 11 L2 IP fuse broken 04 IP phase abnormal 12 L3 IP fuse broken 05 Bypass phase abnormal 21 Line situations are differen...

Page 33: ...ly by the electrical network via the Bypass Remove excess loads from UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove e...

Page 34: ...the connection is ok and the alarm is still displaying please refer to the LCD setting section to enter the neutral loss check menu to see if the parameter3 is CHE if it is please press the Enter key...

Page 35: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 36: ...ortion 2 100 Linear Load 5 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms When phase lock fails 4ms interruption occurs from inverter to bypass Inverter ECO 10 ms EFFICIENCY...

Page 37: ......

Reviews: