29
3-10.Warning Indicator
Warning Description
code
Icon (flashing)
Alarm
Battery is not connected
01
Beeping every second
Over charge
07
Beeping every second
Low battery
08
Beeping every second
Overload
09
Beeping twice every second
Charger failure
0E
Beeping every second
Other warnings
Warning
codes
are
displayed on
.
Refer
to
section 3-11
for
the
details.
Beeping every second
3-11.Warning Code
Warning code
Warning event
Warning code
Warning event
01
Battery unconnected
10
L1 IP fuse broken*
02
IP Neutral loss
11
L2 IP fuse broken*
04
IP phase abnormal
12
L3 IP fuse broken*
05
Bypass phase abnormal
21
Line situations are different in
parallel system
07
Over charge
22
Bypass situations are different in
parallel system
08
Low battery
33
Locked in bypass after overload 3
times in 30 minutes
09
Overload
34
Converter current unbalance
0A
Fan failure
35
Battery fuse broken
0B
EPO enable
3A
Cover of maintain switch is open
0D
Over temperature
3C
Utility extremely unbalanced
0E
Charger failure
3D
Bypass unstable
* These alarms are only for the single input unit.