Installation Drawings
Vertiv
| Liebert
®
EXM
™
TXC
™
User Manual |
17
Figure 10 Outline drawing, Liebert EXM TXC for Liebert EXM, 10-100kVA
Ventilation
TOP
BOTTOM
24" (608mm)
20.4"
(519mm)
15.3"
(387mm)
23.6"
(600mm)
28.3"
(718mm)
39.8" (1010mm)
78.7"
(2000mm)
See Detail A
DETAIL A
34.5"
(876mm)
Leveler
Caster
FRONT
RIGHT SIDE
EXM12009
Rev. 1
Notes
1. 24" [610] minimum clearance above unit for
air exhaust. 36" [914] front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size
and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in
separate conduits.
6. All wiring is to be in accordance with national and
local electrical codes.